Liebert 130 kVA user manual Adding a single module to an existing system

Page 60

User Manual

Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

BATTERY TEST

 

GENERATOR

 

PANEL SETUP

 

>NEXT PAGE

<

PROTOCOLS

ON/OFF UPS CONTROLS RELOAD UPS DATA

>RESET BUFFERS <

RESET ALARM HISTORY RESET EVENT HISTORY

RECTIFIER OFF

 

>RESET ALARMS

<

Select NEXT PAGE and press ENTER key.

Press the ENTER key.

Select RESET ALARMS and press ENTER key.

Return the Display window to normal by repeatedly pressing the ESCAPE key back through the various windows until the default screen is displayed.

These operations resets the logic circuitry to enable the rectifier, inverter and static switch to operate normally.

Note: When the remote EPO switch has been activated it is necessary to manually close the battery circuit breaker.

CAUTION

When the EPO system incorporates a trip facility of the external input a.c. power supply circuit breaker, the RESET switch would have no affect on it. First close the external input a.c. supply circuit breaker, the UPS can be started in the normal manner, as the logic circuits will automatically reset on return of the power supplies.

5.8Adding a single module to an existing system

This procedure should be carried out only by trained service personal.

40

Image 60
Contents Hipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Dear Customer Hipulse Single Phase ‘1+N’ UPS System Rev. No Revision details Hipulse Single Phase ‘1+N’ UPS System Registered Head Office Hipulse Single Phase ‘1+N’ UPS System East Zone Hipulse Single Phase ‘1+N’ UPS System Safety Procedure Hipulse Single Phase ‘1+N’ UPS System General Hipulse Single Phase ‘1+N’ UPS System General Introduction Hipulse Single Phase ‘1+N’ UPS System Operating Instructions Hipulse Single Phase ‘1+N’ UPS System Annexure Hipulse Single Phase ‘1+N’ UPS System Single Module block diagram IntroductionDesign Concept Hipulse Module DesignUPS Power switches configuration Bypass SuppliesReturn of power mains Off-BatteryUPS Module fault Normal OperationMaintenance Bypass OverloadUPS Power Switch Configuration Battery circuit breakerBattery temperature compensation System ExpansionHipulse Single Phase ‘1+N’ UPS System Installation Procedure Battery location Environmental considerationsUPS location Mechanical Considerations Installation Drawings Preliminary ChecksOverall General Arrangement for 130kVA Single Phase UPS Cable Entry Details Power Cabling System ConfigurationBattery cables Module input cablesSafety earth Cable ratingGeneral Notes Cable ConnectionsProtection against earth faults RCD devices Protective devicesSplit Bypass UPS Battery Cabling procedureParallel 1+N Input ConnectionsInput-module Parallel Connections Auxiliary Connections+VE -VE Cable connections for 130 kVA 1Ph UPSBattery Control Control cablesAuxiliary Terminal Block detail Auxiliary Terminal Block X3 and X4 at UPS DescriptionBattery Connection Emergency StopBack Feed Protection Hipulse Single Phase ‘1+N’ UPS System Operator Control and Display Panel UPS Operator Control / Display PanelInverter control switch Single module operator control panelOperator control panel Mimic indicationsMenu Control switches Operator Panel and LCD DisplayOutput Parameters Bargraph SelectionEPO on UPS module Menu OptionsMap of screen display available to operator Or. for Instanc eDefault Window LCD Display Panel Messages Initializing WindowInfo Window Main Menu WindowOption Selection Mode Alarm / Warning MessagesGeneral notes Power Switches ShutdownOn Static Bypass Location of Power Isolators Ecomode the message Load on Bypass will not appear Battery C.B. Open Bypass Switch Open Ecomode Your load is now powered via the Static Bypass system Normal OperationYour load is now powered via the Static Bypass system Procedure for completely powering down the UPS UPS is now completely powered down Adding a single module to an existing system If YOU are not Sure What YOU are Doing Then do not do IT Ecomode INV OFF VIA Display Load on Bypass Setting the Battery Test Language Selection Changing the current Date and TimeHipulse Single Phase ‘1+N’ UPS System Battery Installation SafetyUPS Batteries Temperature considerations Battery populationBattery protection Battery RacksConnecting the Battery IntroductionBattery Supply To UPS Cabinet Battery Installation Battery circuit breakerBattery Control and Power Connections Battery temperature Board Display Panel Interpretation LED InterpretationProcedure to carry out the reset see Operating Instructions Sr. No Display Message Alarm Interpretation Display Panel MessagesBypass Switch Open BYP. Absent Battery Under Test BYP Xfer Count Block Hipulse Single Phase ‘1+N’ UPS System + N System General1+N System block diagram with Separate Batteries BatteryInstallation procedure Connection of 1+N system parallel single bus cablesInter-module control Connection of EPO Push Button System Start-up and shutdown procedures Separate Batteries Operating InstructionDefault window Hipulse Single Phase ‘1+N’ UPS System Display Panel message interpretation in 1+N System Complete system shutdownUPS Mechanical Characteristics Conformity and StandardUPS Environmental UPS Electrical Characteristics C T I F I E R I N P U T M a I N SUPS Electrical Characteristics DC Intermediate Circuit Rated Power KVA 130UPS Electrical Characteristics Inverter Output V E R T E R O U T P U TUPS Electrical Characteristics Bypass Input Mains Protection, bypass lineHipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Remote Alarm Monitor RAM ConnectionsUPS 220/240V AC 50 HzTermination Indication & MeteringProtection Bypass Isolation Cubicle