| Hipulse - Single Phase ‘1+N’ UPS System | 130 kVA - 110V | |
30. | BYP: XFER COUNT BLOCK | This message informs the operator that the load has been | |
|
|
| transferred to the bypass more than eight times in one minute. |
|
|
| After eight transfers the load will remain on bypass. This message |
|
|
| could be initiated by a load causing the UPS to overload, it requires |
|
|
| investigation. |
|
|
| |
| 31. | BATTERY: GROUND FALUT | This message informs the operator that the battery is not longer |
|
|
| isolated from ground and there is danger of electrocution. |
32. | BACKFEED FAULT | This message informs the operator that the failure of the bypass |
|
| static devices has resulted in voltage being fed back to the bypass |
|
| supply input. |
In addition to the above message there are a number of software alarms (i.e. BAD EEPROM,