Hipulse - Single Phase ‘1+N’ UPS System | 130 kVA - 110V |
WARNING
If the load equipment will not be ready to accept power on the arrival of the commissioning engineer then ensure that the system output cables are safely isolated at their ends.
6.Connect the Battery cables between the UPS terminals (+/
As a safety precaution remove the battery fuse in the module until the arrival of commissioning engineer.
OBSERVE THE BATTERY CABLE POLARITY
WARNING
Do not close the battery circuit breaker before the equipment has been commissioned.
Input-module Parallel Connections:
7.1+N Parallel UPS System: Inside the module there is an Parallel Connectors Board mounted on the left hand side. Connect one end of the interconnecting ribbon cables to interface connector (X1) of the first UPS module and the other end to connector (X2) of the second module, and so to the next module until a closed loop is formed. (see fig
Auxiliary Connections:
8.Connect the auxiliary cables of any external interface/ signals to the respective connections of the output auxiliary terminal block (X4).
9.Refit the lower protective cover.