Hipulse - Single Phase ‘1+N’ UPS System | 130 kVA - 110V |
10.3 BYPASS ISOLATION CUBICLE
10.3.1Introduction
Bypass Isolation Cubicle is placed in the Bypass input path of the UPS. It consist of VEE Connected
10.3.2Termination
The Incoming Supply from the Customers distribution is fed as input to the Bypass Isolation Cubicle. The incoming supply 3ph,4wire is fed to RI ,SI,TI,NI terminals .
The output of the cubicle is available on the RU, NU terminals . which is fed 1 phase Bypass Supply to the UPS Panel.
10.3.3Indication & Metering
LED’s are used to monitor availability of Input voltage before the Vee Connected Transformer and after it ,which are seen on the Mimic Panel
Output voltage and Phase current is measured using Voltmeter & Current meter which are seen on the Mimic Panel .
10.3.4Protection
Incoming 3 pole MCCB is used as Protective Device before the Vee Connected transformer ,Control fuses are used for protection of Voltmeter.
Utility socket is provide for single phase supply.