American Power Conversion PX user manual Redundant Intelligence Module Replacement

Page 63

Chapter 8 - Module Replacement

Main Intelligence Module Replacement

1.Remove the grill cover from the top level of the Power Array. The intelligence module resides under the redundant intelligence module in the upper right corner of the frame.

Note: If a functioning RIM is installed, it will provide limited control of the SymmetraTM until the replacement MIM is installed. If a functioning RIM is not installed, either the SymmetraTM must be placed in manual bypass mode or the load equipment must be switched off. To place the SymmetraTM in manual bypass, switch the maintenance bypass switch to the “on” position.

Important: When the SymmetraTM is in bypass mode, the load equipment is unprotected from power failure.

2.Use a flathead screwdriver to release the flip latch.

3.Unscrew and release the retaining screws.

4.Slide the MIM out of the frame.

Installing the Replacement Main Intelligence Module

Refer to Chapter 5 for the MIM installation procedure.

Note: If SymmetraTM was placed in manual bypass in step 1 above, return to normal operation by switching the maintenance bypass switch back to the “off” position.

Replacement MIM Verification

From the startup screen, press any key to open the top level menu screen. Follow the sequence in figure 8-10 to ensure that the replacement MIM is functioning properly. (Status: On & OK).

Fig 8-10 Intelligence Module Verification

Redundant Intelligence Module Replacement

1.Remove the grill cover from the top level of the Power Array. The redundant intelligence module resides above the intelligence module in the upper right corner of the frame.

Note. A RIM can only be replaced if a functioning MIM is in- stalled or the load equipment is switched off.

2.Use a flathead screwdriver to release the flip latch.

3.Unscrew and release the retaining screws.

4.Slide the RIM out of the frame.

Installing the Replacement Redundant Intelligence Module

Refer to Chapter 5 for the RIM installation procedure.

Note: A RIM alone is not adequate to restart the SymmetraTM. Make sure a functioning MIM is installed.

Replacement Redundant Intelligene Module Verification

From the startup screen, press any key to open the top level menu screen. Follow the sequence in figure 8-11 to ensure that the replacement RIM is functioning properly. (Status: On & OK).

Fig 8-11 Redundant Intelligence Module Verification

8-4

Image 63
Contents Page 0660 Main Tech Support+353 91 Toll-Free NumbersRadio Frequency Interference Important Safety InstructionsLife Support Policy Limited WarrantyTable of Contents Index MiniFrame MasterFrame IntroductionTheory of Operation Power Processing Battery SourceFig I-2 Functional Diagram of a SymmetraTM Thank You SymmetraTM OverviewPower Processing System Battery SourceControl/User Interface Load-Disconnect Mode On-Line Operating ModeModes of Operation Bypass Operating Mode On-Battery Operating ModeImportant Information DefinitionsPage Important Safety Information Safety InformationSafety Earth Ground Indicates the pri- mary safety ground Symbols Used In This ManualSafety-2 Physical Representation Bays Power Array FrameFive Four Power Battery ModulePower Module Powerview User InterfacePower Module Battery ModuleInput Circuit Breaker Maintenance Bypass SwitchMain Intelligence Module MIM Redundant Intelligence Module RIMRear View of a Power Array Site Preparation BTU Output Space and Weight ConsiderationsTransporting Power Array to Installation Site Operating ConditionsSite Preparation Unpacking and Installing Frame Check For Damage Dimensions WeightInitial Inspection Move the FrameMoving Battery & Power Modules Remove Packing MaterialsRemove the Frame from the Pallet Wiring Requirements & Procedures Repo Switch Wiring SymmetraTM WiringInput Wiring Output WiringInput Wiring Input Wiring SpecificationsInput Wiring Procedures Ground Wiring and Input Wiring Terminal Blocks Ground Wiring Terminal BlockOutput Wiring Installation Output WiringCable Specifications Remote Emergency Power Off SwitchRepo Specifications Repo Switch InstallationVdc Repo Switch Connection Electrical Wiring TestElectrical Wiring Test/Checklist Contact Closure Repo Switch Connection11 Startup Screen Record the PowerView reportedSetting Up The Power Array Positions Setup of Power ArrayFrame Leveling Procedure Removing Grill CoversBattery Module Location of Battery Module Bays Installing the Battery ModulesProcedure for Battery Module Installation Clear all battery module bays of any debrisProcedure for Power Module Installation Installing the Power Modules10 Location of the MIM and RIM Installing the Main Intelligence Module MIMInstalling the Redundant Intelligence Module RIM Main Intelligence ModuleRemove the grill cover from the top level of the frame Installing the PowerView InterfaceRemote Placement of the PowerView Wall Mounting the PowerViewSmartSlotTM Interface Accessories Installation Test/Checklist Installation TestPower Reported SymmetraTM Power Module/Frame Capacities21 Miscellaneous Status Screen 22 Power The Load Sequence 25 Return to On-Line Mode System Setup PowerView Display Physical Features of the Powerview PowerView FunctionsPowerView Interface Navigation Keys PowerView LED IndicatorsSymbol Name Function of Key On Key EscStatus Startup ScreenTop-Level Menu Screen ControlLogging SetupAccessories DiagnosticsConfiguring & Operating the SymmetraTM Introduction Powering the Power ArrayLoad With No Redundancy Status Screen Powering the LoadsReview Status Conditions Voltage Status ScreenLoad With Redundancy Status Screen Battery Status Screen Power Status ScreenFrequency Status Screen Miscellaneous Status Screen Alarm Threshold Status Screen11 Sample Alarm Threshold Status Screen Perform a Self TestShutdown Parameter Selection Screen Configure AlarmsAlarm Thresholds Selection Screen Switching Audible Alarm Beeper OffEvent Log Screen Review Diagnostic InformationDiagnostics Menu Screen Review Logging MenuModule Replacement Module Replacement Module Failure Alarm IndicatorsReturning Modules to APC Battery Module Replacement Installing the Replacement ModuleReplacement Battery Module Verification Power Module Replacement Replacement Module VerificationRefer to for the power module installation proce- dure Installing the Replacement Redundant Intelligence Module Redundant Intelligence Module ReplacementInstalling the Replacement Main Intelligence Module Replacement MIM VerificationPowerView Interface Messages PowerView Meaning Corrective Action Message Start-Up MIM detects the RIM beforeRIM is awake Has been corrected either because PowerView Meaning Corrective Action Message# of batteries decreased Load is No Longer aboveRedundancy-select Setup-Alarms-RedundancyThreshold. Startup-Setup-Alarms Select zeroBecause of a power failure, wait for Battery modules are beingSupport. See inside front cover PowerView Display Messages Index Configuring PowerView Threshold status Electro-static discharge, 2-1 Emergency power offDescription Frame, 2-1 Modules ConfiguringDescription, 1-4 Installation Ordering information Checklist Input Output Overview RepoReplacement Modules & Accessories English Text