American Power Conversion PX PowerView Meaning Corrective Action Message Start-Up, RIM is awake

Page 65

Chapter 9 - PowerView Display Messages

 

PowerView

Meaning

Corrective Action

 

Message

 

 

 

 

 

 

 

Start-Up

#Pwr modules changed

At least one power module has

No corrective action necessary.

 

since last ON.

been added, or removed from

Proceed with the startup.

 

 

the SymmetraTM since the last

 

 

 

time the Pwr ON command

 

 

 

was issued.

 

 

 

 

 

 

#Batteries changed since

At least one battery module

No corrective action necessary.

 

last ON.

has been added, or removed

Proceed with the startup.

 

 

from the SymmetraTM since

 

 

 

the last time the Pwr ON

 

 

 

command was issued.

 

 

 

 

 

 

No Redundant

There is no RIM installed.

Proceed with the startup, or abort

 

Intelligence Module.

Note: This message sometimes

the startup, and install a RIM.

 

 

occurs at powerup because the

Note: Without a functioning RIM,

 

 

MIM detects the RIM before

there is no redundancy in the event

 

 

the RIM is "awake."

of a MIM failure.

 

 

 

 

 

Batt capacity less than

The battery capacity of the

Option #1: Abort the startup, and

 

Return Batt Cap

SymmetraTM is less than the

allow batteries to recharge.

 

 

user specified minimum

Option #2: Continue startup,

 

 

battery capacity required to

with less than minimum battery

 

 

turn on the load.

capacity.

 

 

 

 

 

Input Freq outside

The input frequency to the

Option #1: Improve the

 

configured range

SymmetraTM is outside the

frequency of the incoming voltage.

 

 

configured range. The output

Option #2: Widen the range of

 

 

frequency will not

the acceptable incoming

 

 

synchronize with the input

frequency with the PowerView.

 

 

frequency. Normal bypass is

(Startup-Setup-OutputFreq-Select.)

 

 

not available.

Option #3: Proceed with startup.

 

 

 

Normal bypass is not available.

 

 

 

 

 

AC adequate for UPS

The SymmetraTM will function

Option #1: Improve the incoming

 

but not for bypass

online with the input voltage,

voltage.

 

 

but in the event that bypass is

Option #2: Proceed with startup.

 

 

required, the input voltage is

Normal bypass is not available.

 

 

not adequate to power the

 

 

 

load equipment.

 

 

 

 

 

 

Low/No AC input,

Input voltage is not adequate

Option #1: Abort startup until

 

startup on battery

to start the SymmetraTM. If

acceptable input voltage is present.

 

 

startup proceeds, SymmetraTM

Option #2: Proceed with startup.

 

 

will function from battery.

Battery will be discharged.

 

 

 

 

9-1

Image 65
Contents Page +353 91 Main Tech SupportToll-Free Numbers 0660Radio Frequency Interference Important Safety InstructionsLife Support Policy Limited WarrantyTable of Contents Index MiniFrame MasterFrame IntroductionFig I-2 Functional Diagram of a SymmetraTM Power Processing Battery SourceThank You SymmetraTM Overview Theory of OperationControl/User Interface Power Processing SystemBattery Source Modes of Operation Load-Disconnect ModeOn-Line Operating Mode Bypass Operating Mode On-Battery Operating ModeImportant Information DefinitionsPage Important Safety Information Safety InformationSafety Earth Ground Indicates the pri- mary safety ground Symbols Used In This ManualSafety-2 Physical Representation Five Four Power Battery Power Array FrameModule BaysPower Module Powerview User InterfaceBattery Module Power ModuleMain Intelligence Module MIM Maintenance Bypass SwitchRedundant Intelligence Module RIM Input Circuit BreakerRear View of a Power Array Site Preparation Transporting Power Array to Installation Site Space and Weight ConsiderationsOperating Conditions BTU OutputSite Preparation Unpacking and Installing Frame Initial Inspection Dimensions WeightMove the Frame Check For DamageRemove the Frame from the Pallet Moving Battery & Power ModulesRemove Packing Materials Wiring Requirements & Procedures Input Wiring SymmetraTM WiringOutput Wiring Repo Switch WiringInput Wiring Procedures Input WiringInput Wiring Specifications Ground Wiring and Input Wiring Terminal Blocks Ground Wiring Terminal BlockOutput Wiring Installation Output WiringRepo Specifications Remote Emergency Power Off SwitchRepo Switch Installation Cable SpecificationsElectrical Wiring Test/Checklist Electrical Wiring TestContact Closure Repo Switch Connection Vdc Repo Switch Connection11 Startup Screen Record the PowerView reportedSetting Up The Power Array Frame Leveling Procedure Setup of Power ArrayRemoving Grill Covers PositionsProcedure for Battery Module Installation Installing the Battery ModulesClear all battery module bays of any debris Battery Module Location of Battery Module BaysProcedure for Power Module Installation Installing the Power ModulesInstalling the Redundant Intelligence Module RIM Installing the Main Intelligence Module MIMMain Intelligence Module 10 Location of the MIM and RIMRemote Placement of the PowerView Installing the PowerView InterfaceWall Mounting the PowerView Remove the grill cover from the top level of the frameSmartSlotTM Interface Accessories Installation Test/Checklist Installation Test21 Miscellaneous Status Screen 22 Power The Load Sequence Power ReportedSymmetraTM Power Module/Frame Capacities 25 Return to On-Line Mode System Setup PowerView Display PowerView Interface Physical Features of the PowerviewPowerView Functions Symbol Name Function of Key On Key PowerView LED IndicatorsEsc Navigation KeysTop-Level Menu Screen Startup ScreenControl StatusAccessories SetupDiagnostics LoggingConfiguring & Operating the SymmetraTM Introduction Powering the Power ArrayReview Status Conditions Powering the LoadsVoltage Status Screen Load With No Redundancy Status ScreenFrequency Status Screen Load With Redundancy Status Screen Battery Status ScreenPower Status Screen 11 Sample Alarm Threshold Status Screen Alarm Threshold Status ScreenPerform a Self Test Miscellaneous Status ScreenAlarm Thresholds Selection Screen Configure AlarmsSwitching Audible Alarm Beeper Off Shutdown Parameter Selection ScreenDiagnostics Menu Screen Review Diagnostic InformationReview Logging Menu Event Log ScreenModule Replacement Returning Modules to APC Module ReplacementModule Failure Alarm Indicators Replacement Battery Module Verification Battery Module ReplacementInstalling the Replacement Module Refer to for the power module installation proce- dure Power Module Replacement Replacement Module Verification Installing the Replacement Main Intelligence Module Redundant Intelligence Module ReplacementReplacement MIM Verification Installing the Replacement Redundant Intelligence ModulePowerView Interface Messages RIM is awake PowerView Meaning Corrective Action Message Start-UpMIM detects the RIM before # of batteries decreased PowerView Meaning Corrective Action MessageLoad is No Longer above Has been corrected either becauseThreshold. Startup-Setup-Alarms Setup-Alarms-RedundancySelect zero Redundancy-selectBecause of a power failure, wait for Battery modules are beingSupport. See inside front cover PowerView Display Messages Index Description Configuring PowerView Threshold statusElectro-static discharge, 2-1 Emergency power off Description, 1-4 Installation Ordering information ConfiguringChecklist Input Output Overview Repo Frame, 2-1 ModulesReplacement Modules & Accessories English Text