Chapter 9 - PowerView Display Messages
| PowerView | Meaning | Corrective Action | |
| Message | |||
|
|
| ||
|
|
|
| |
Module | Bad Battery Module | A battery module has failed, | Refer to Chapter 8 for module | |
Failure | and requires replacement. | replacement procedure. | ||
| ||||
|
|
|
| |
| Bad Power Module | A power module has failed, | Refer to Chapter 8 for module | |
| and requires replacement. | replacement procedure. | ||
|
| |||
|
|
|
| |
| Intelligence Module is | The main intelligence module | Refer to Chapter 8 for module | |
| has failed, and requires | |||
| installed and failed | replacement procedure. | ||
| replacement. | |||
|
|
| ||
|
|
|
| |
| Redundant Intelligence | The redundant intelligence | Refer to Chapter 8 for module | |
| Module is installed and | module has failed, and | ||
| replacement procedure. | |||
| failed | requires replacement. | ||
|
| |||
|
|
|
| |
Threshold | Load is above kVA alarm | The load has exceeded the | Option #1: Reduce the load. | |
user specified load alarm | Option #2: Use the PowerView to | |||
Alarm | threshold | |||
threshold. | raise the alarm threshold. | |||
|
| |||
|
|
|
| |
|
|
| Option #1: If possible, install | |
|
| SymmetraTM no longer detects | additional power modules. | |
|
| Option #2: Decrease the load. | ||
|
| redundant power modules. | ||
| Redundancy has been | Option #3: Disable the | ||
| Either power module(s) have | |||
| lost. | redundancy alarm by setting | ||
| failed, or the load has | |||
|
| redundancy to zero. (Startup- | ||
|
| increased. | ||
|
|
| ||
|
|
| ||
|
|
| select zero.) | |
|
|
|
| |
|
| Actual power module | Option #1: If possible, install | |
|
| additional power modules. | ||
|
| redundancy has fallen below | ||
|
| Option #2: Decrease the load. | ||
| Redundancy is below | the user specified redundancy | ||
| Option #3: Use the PowerView to | |||
| alarm threshold. | alarm threshold. Either | ||
| decrease the redundancy alarm | |||
|
| power module(s) have failed, | ||
|
| threshold. | ||
|
| or the load has increased. | ||
|
|
| ||
|
|
| ||
|
|
|
| |
|
|
| Option #1: Allow the battery | |
|
| The predicted runtime is | modules to recharge. | |
|
| Option #2: If possible, increase | ||
|
| lower than the user specified | ||
|
| the number of battery modules. | ||
| Runtime is below alarm | minimum runtime alarm | ||
| Option #3: Decrease the load. | |||
| threshold. | threshold. Either the battery | ||
| Option #4: Use the PowerView to | |||
|
| capacity has decreased, or the | ||
|
| decrease the minimum runtime | ||
|
| load has increased. | ||
|
| alarm threshold. | ||
|
|
| ||
|
|
| ||
|
|
|
| |
Bypass |
| The frequency and/or voltage | Option #1: Decrease the | |
|
| is out of acceptable range for | ||
|
| sensitivity to input frequency. | ||
|
| bypass. This message occurs | ||
| Bypass is not in range | |||
| when SymmetraTM is on line, | |||
| (either freq or voltage) | Option #2: Corrrect input voltage | ||
| and indicates that the bypass | |||
|
| to provide acceptable voltage | ||
|
| mode may not be available if | ||
|
| and/or frequency. | ||
|
| required. | ||
|
|
| ||
|
|
|
| |
| Bypass contactor stuck | SymmetraTM is stuck in the | Call your contract service | |
| bypass position, and cannot go | provider, or APC Technical | ||
| in bypass position. | |||
| online. | Support. (See inside front cover.) | ||
|
| |||
|
|
|
| |
|
|
|
|