Chapter 4 - Electrical Requirements and Procedures

Remote Emergency Power Off Switch

The Power Array can be de-energized with a remote emer- gency power off (REPO) switch. REPO switches are com- mon in computer rooms where, for safety reasons, power to the loads must be quickly disconnected. The REPO switch physically flips the system enable switch to “stand by” mode. This cuts power to the main intelligence module, which in turn cuts power to the Power Array and to the load equip- ment. The system enable switch must be physically reset.

IMPORTANT: The system enable switch cuts power to the in- telligence module only. All internal circuitry that is connected to incoming utility (mains) voltage is still powered if incoming utility power is still present.

The REPO can be connected to either a switched, 24Vdc cir- cuit, or a simple contact closure.

REPO Specifications

The REPO circuit is considered a Class 2 and SELV circuit. SELV is an acronym for “Safety Extra Low Voltage.” SELV is a common term in Europe and IEC standards. A SELV circuit is isolated from primary circuitry through an isolating trans- former and designed so that under normal conditions, the voltage is limited to 42.4 Vpeak or 60 Vdc.

A Class 2 Circuit is a common term in North America and in UL and CSA standards. It is defined in the Canadian Electri- cal Code (C22.1, Section 16) and in the National Electrical Code (NFPA 70, Article 725).

SELV and Class 2 circuits must be isolated from all primary circuitry. Do not connect any circuit to the EPO terminal block unless it can be confirmed that the circuit is SELV or Class 2. If there is a question, use a contact closure switch.

Cable Specifications

The cable that connects SymmetraTM to the Emergency Power Off switch should be one of the following UL Listed types: CL2 - Class 2 cable for general purpose use; or

CL2P - Plenum cable for use in ducts, plenums, and other space used for environmental air; or

CL2R - Riser cable for use in a vertical run in a shaft or from floor to floor; or

CL2X - Limited Use cable for use in dwellings and for use in raceway.

For installation in Canada, the cable should be CSA Certi- fied, type ELC (Extra-Low-Voltage Control Cable).

REPO Switch Installation

nVerify that all incoming line voltage (mains power) and low voltage (control) circuits are de-energized and locked out before installing cables or making connec- tions, whether in the junction box or to the SymmetraTM Power Array.

nAlways verify that all battery modules are removed and all battery extension frames are disconnected from the Power Array before installing any wiring to the Power Array.

REPO Wiring Procedures

1.Refer to figure 4-8. Remove the screw holding the two- piece access panel at the rear of the Power Array. Remove the panel. Set the screw and the panel pieces aside.

Fig 4-8 Removal of REPO Wiring Panels

2.Refer to figures 4-9 and 4-10. Select the configuration that matches the type of REPO switch that is to be installed. Note: An existing jumper must be removed from the terminal block if a 24Vdc REPO switch (figure 4-10) is to be installed.

3.Extend the wiring from the switch to the Power Array. Strip

13mm (1/2") of insulation from the end of each of the in- coming wires.

4.Feed the wires through the knockout in the access panel, and install a strain relief (Romex) connector.

5.Make sure there are no loose strands and that the terminal connection screws are sufficiently tightened.

6.After the electrical wiring test/checklist at the end of this chapter is completed, replace the REPO access panel.

4-5

Image 33
Contents Page +353 91 Main Tech SupportToll-Free Numbers 0660Radio Frequency Interference Important Safety InstructionsLife Support Policy Limited WarrantyTable of Contents Index MiniFrame MasterFrame IntroductionFig I-2 Functional Diagram of a SymmetraTM Power Processing Battery SourceThank You SymmetraTM Overview Theory of OperationPower Processing System Battery SourceControl/User Interface Load-Disconnect Mode On-Line Operating ModeModes of Operation Bypass Operating Mode On-Battery Operating ModeImportant Information DefinitionsPage Important Safety Information Safety InformationSafety Earth Ground Indicates the pri- mary safety ground Symbols Used In This ManualSafety-2 Physical Representation Five Four Power Battery Power Array FrameModule BaysPower Module Powerview User InterfaceBattery Module Power ModuleMain Intelligence Module MIM Maintenance Bypass SwitchRedundant Intelligence Module RIM Input Circuit BreakerRear View of a Power Array Site Preparation Transporting Power Array to Installation Site Space and Weight ConsiderationsOperating Conditions BTU OutputSite Preparation Unpacking and Installing Frame Initial Inspection Dimensions WeightMove the Frame Check For DamageMoving Battery & Power Modules Remove Packing MaterialsRemove the Frame from the Pallet Wiring Requirements & Procedures Input Wiring SymmetraTM WiringOutput Wiring Repo Switch WiringInput Wiring Input Wiring SpecificationsInput Wiring Procedures Ground Wiring and Input Wiring Terminal Blocks Ground Wiring Terminal BlockOutput Wiring Installation Output WiringRepo Specifications Remote Emergency Power Off SwitchRepo Switch Installation Cable SpecificationsElectrical Wiring Test/Checklist Electrical Wiring TestContact Closure Repo Switch Connection Vdc Repo Switch Connection11 Startup Screen Record the PowerView reportedSetting Up The Power Array Frame Leveling Procedure Setup of Power ArrayRemoving Grill Covers PositionsProcedure for Battery Module Installation Installing the Battery ModulesClear all battery module bays of any debris Battery Module Location of Battery Module BaysProcedure for Power Module Installation Installing the Power ModulesInstalling the Redundant Intelligence Module RIM Installing the Main Intelligence Module MIMMain Intelligence Module 10 Location of the MIM and RIMRemote Placement of the PowerView Installing the PowerView InterfaceWall Mounting the PowerView Remove the grill cover from the top level of the frameSmartSlotTM Interface Accessories Installation Test/Checklist Installation TestPower Reported SymmetraTM Power Module/Frame Capacities21 Miscellaneous Status Screen 22 Power The Load Sequence 25 Return to On-Line Mode System Setup PowerView Display Physical Features of the Powerview PowerView FunctionsPowerView Interface Symbol Name Function of Key On Key PowerView LED IndicatorsEsc Navigation KeysTop-Level Menu Screen Startup ScreenControl StatusAccessories SetupDiagnostics LoggingConfiguring & Operating the SymmetraTM Introduction Powering the Power ArrayReview Status Conditions Powering the LoadsVoltage Status Screen Load With No Redundancy Status ScreenLoad With Redundancy Status Screen Battery Status Screen Power Status ScreenFrequency Status Screen 11 Sample Alarm Threshold Status Screen Alarm Threshold Status ScreenPerform a Self Test Miscellaneous Status ScreenAlarm Thresholds Selection Screen Configure AlarmsSwitching Audible Alarm Beeper Off Shutdown Parameter Selection ScreenDiagnostics Menu Screen Review Diagnostic InformationReview Logging Menu Event Log ScreenModule Replacement Module Replacement Module Failure Alarm IndicatorsReturning Modules to APC Battery Module Replacement Installing the Replacement ModuleReplacement Battery Module Verification Power Module Replacement Replacement Module VerificationRefer to for the power module installation proce- dure Installing the Replacement Main Intelligence Module Redundant Intelligence Module ReplacementReplacement MIM Verification Installing the Replacement Redundant Intelligence ModulePowerView Interface Messages PowerView Meaning Corrective Action Message Start-Up MIM detects the RIM beforeRIM is awake # of batteries decreased PowerView Meaning Corrective Action MessageLoad is No Longer above Has been corrected either becauseThreshold. Startup-Setup-Alarms Setup-Alarms-RedundancySelect zero Redundancy-selectBecause of a power failure, wait for Battery modules are beingSupport. See inside front cover PowerView Display Messages Index Configuring PowerView Threshold status Electro-static discharge, 2-1 Emergency power offDescription Description, 1-4 Installation Ordering information ConfiguringChecklist Input Output Overview Repo Frame, 2-1 ModulesReplacement Modules & Accessories English Text