Start-Up - Economizer (optional)
Note
To prevent premature heat exchanger failure, do not locate units where chlorinated, halogenated, or acid vapors are present.
Note
Units with an economizer are designed for either
Note
Note
Economizer control may use outside air temperature reference
Note
Economizer control may use a potentiometer (MB‑1),
1. Verify Sensor Installation
All economizer options (EC) require an outdoor air temperature or enthalpy sensor to be
Economizer options
Verify that all economizer sensors needed for your application are properly installed and wired.
2. Set Minimum Outside Air
Set the minimum outside air position.
All economizer options,
The potentiometer is located on the economizer for options
32Model IG / IGX
important
The outside air volume must be measured and compared to the total air volume when setting the minimum outside air. The minimum outside air should never be set based on the inlet damper or potentiometer position.
3.Set the Enthalpy Changeover Set Point (optional)
If using an economizer, the enthalpy changeover setting must be set. If differential temperature or differential enthalpy control is used, set the enthalpy changeover set point to D. If outside air temperature or enthalpy reference is used, set the enthalpy changeover set point to the desired setting from the following table.
Enthalpy Changeover Setting
Setting | Changeover | |
Temperature* (°F) | ||
| ||
|
| |
A | 73 | |
|
| |
B | 70 | |
|
| |
C | 67 | |
|
| |
D | 63 | |
|
|
*Temperature at 50% relative humidity, see the Honeywell W7212 Economizer instructions for set points at other humidities
Note
For options
4. Program Optional Room Stat
Program the optional room stat. Separate detailed instructions for programming the room stat ship with the optional room stat.
®