Troubleshooting
Evaporative Cooler does not Operate (Recirculating pump)
Supply fan must be on for cooler to operate
24 VAC between terminals
Y1 and X
Yes
24 VAC between terminal A2 on
Cooling Relay (RC) and X
Yes
115 VAC between terminals
102 and 101
Yes
115 VAC between terminal
114 and 101
No
No
No
No
Cool switch (S4) off
(turn cool switch (S4) on)
Cool switch not wired
(wire cool switch (S4))
Optional inlet air sensor (TS4) holding
(Adjust TS4 setting. Reference Blower
Cooling transformer (TR4) defective
(Replace transformer)
Cooling relay (RC) is not energized
(Check for loose connections)
(Repair or replace relay)
Yes
At this time the evaporative cooler pumps should be on
Water Blows through Evaporative Cooler
Are the headers in place and | No |
| |
located near the entering |
| ||
|
| ||
air side of the media? |
|
| |
|
|
|
|
| Yes |
|
|
|
|
| |
|
|
|
|
Water supply greater than | Yes |
| |
evaporation and |
|
| |
|
|
|
|
| No |
|
|
|
|
|
|
Air velocity greater than | Yes |
| |
specified? |
|
| |
|
| ||
|
|
|
|
| No |
|
|
|
|
| |
|
|
|
Replace headers and/or move the headers
Use the main supply valve to reduce the supply of water
Reduce the air velocity through the media
(Reference Blower
At this time the evaporative cooler should be operating without water blowing through
56 Model IG / IGX
®