Installation of Concentric Venting (General)
Concentric venting allows the exhaust pipe and combustion air pipe to pass through a single hole in the roof or wall of the building. A concentric venting adapter (CVA) is required for concentric venting.
The concentric venting adapter is designed for indoor installations and should never be installed on the exterior of the building.
The exhaust pipe must terminate with the vent terminal. For horizontal venting, the combustion air pipe must terminate with the combustion air guard. For vertical venting, the combustion air pipe must terminate with the inlet terminal. Depending on what was ordered, one of these vent terminals will be provided in the optional venting kit along with the concentric venting adapter (CVA).
If venting vertically through the roof, refer to the vertical concentric venting instructions. If venting horizontally through the wall, refer to the horizontal concentric venting instructions.
note
Vent piping is supplied by others and not supplied by manufacturer.
|
|
Venting Adapter | Venting Adapter |
Combustion Air Connection | Exhaust Connection |
Concentric Side | Concentric Side |
CVA
Combustion Air Connection | Exhaust Connection |
Top View
10Model IG / IGX
Concentric Venting – Horizontal
Refer to the diagram below for venting on horizontal concentric systems. Maintain at least 12 inches from the combustion air inlet guard to the exhaust vent terminal (Dim. B). To prevent water from running into the combustion air pipe and to allow for easy installation of the combustion air inlet guard, the combustion air pipe must terminate at least 2 inches from the exterior surface of the outside wall (Dim. A).
A = 2 inch minimum |
| Exterior | |
B = 12 inch minimum |
| ||
|
| Wall | |
|
|
|
Mounting |
|
|
Bracket |
|
|
| A | B |
EXHAUST |
|
|
COMBUSTION AIR |
| Exhaust |
| Vent | |
|
| Terminal |
Mounting |
|
|
Bracket | Combustion | |
| ||
Pitch vent pipe downward | Air Inlet Guard | |
from furnace 1/4 inch per foot |
|
|
Vent Connection Diameter
Vent terminals must be used (one vent terminal included with each furnace). Construct the vent system as shown in the drawings and refer to the table for the correct vent connection diameters.
| Concentric Vent | |||
| Connection Diameter | Connection Diameter | ||
Furnace | Exhaust | Combustion Air | Exhaust | Combustion Air |
Size (MBH) | (inches) | (inches) | (inches) | (inches) |
4 | 4 | 4 | 6 | |
6 | 6 | 6 | 8 |
Vent Length
Refer to table for minimum and maximum vent lengths. The total equivalent vent length must include elbows. The equivalent length of a 4 inch elbow is
6 feet and the | Vent | Minimum | Maximum | |
equivalent length | ||||
Length | (feet) | (feet) | ||
of a 6 inch elbow | ||||
Horizontal | 5 | 70 | ||
is 10 feet. | ||||
|
|
|
1. Determine Venting Location
Determine the location of the concentric venting adapter (CVA) based on any clearances that must be maintained (follow all codes referenced in these instructions).
2. Attach Mounting Brackets
Attach
®