6. Wire the Evaporative Cooler (optional)
Reference the ladder diagram on the inside of the control center door for correct wiring of the pump and the optional water valves.
note
Large evaporative coolers may require a separate power supply.
7. Install Economizer Sensors (optional)
All economizer options (EC) require an outdoor air temperature or enthalpy sensor to be field installed inside of the weatherhood and field wired to terminals SO+ and SO- on the economizer.
Economizer options
The sensors are provided by the factory and ship with the unit.
8. Install Discharge Air Sensor (optional)
For units with 8:1, 16:1 or 24:1 staged turndown, install the discharge air sensor at least three duct diameters downstream of the heat exchanger. The discharge air sensor can be found in the unit’s control center.
9. Install DDC Interface (Optional)
Some units may use an external signal from a building management system to control the dampers and/or discharge air temperature. Reference the unit ladder diagram for the correct wiring.