Troubleshooting
Motor Over Amps
Air volume too high?
No
Actual static pressure
lower than design?
No
Blower rotation correct?
Yes
Motor voltage correct?
Yes
Motor horsepower too low?
No
Shorted windings in motor?
Yes
Everything is working
properly, consult factory.
Yes
Yes
No
No
Yes
Yes
Adjust drives or increase external static pressure as needed.
(Reference Blower
Adjust drives to reduce blower RPM.
(Reference Blower
Reverse blower rotation.
(Reference Blower
Provide proper power supply.
(Reference Blower
Resize motor.
Replace motor.
®
Model IG / IGX