Check Operation - Recirculating Units (optional)
NOTE
Blower
Recirculation Operation
The recirculation operation option is recommended when the ventilation equipment provides the primary source of heating for the space. Recirculation can
Building Pressure Control - a
modulating spring return actuator is used to control the return air amounts. The return air damper modulates from fully open to fully closed based on a signal from a remote pressure sensing device.
Turn both knobs to the upper most pressure setting. You may have to remove the outdoor pressure tap tubing. The return air damper should close.
BLOWER
EXHAUST
(OPTIONAL)
SUPPLY
|
| MAIN VALVES |
HEAT |
| |
|
| DIRTY FILTERS |
75 | 70 |
|
80 | 65 | (OPTIONAL) |
85 | 60 | |
90 | 55 |
|
PHOTOHELIC
Building
Pressure Control
vary from 100% return air to 100% outside air. Control strategies include
Before the unit is left in service, the recirculation control system should be tested.
Set both knobs at the lowest setting and the damper should open. It may take one to two minutes for the damper to reach the desired position.
Reset the correct pressure limits before starting the unit.
2-Position Damper
A
to closed. If power is cut to the unit, | EXHAUST | BLOWER | |
the outdoor air damper will fail to |
| (OPTIONAL) |
|
SUPPLY |
| ||
|
|
| |
close. | HEAT |
| MAIN VALVES |
|
| ||
|
|
| |
Turn the recirculating switch on | RECIRCULATION |
| |
|
|
| |
the remote control panel to each |
|
| DIRTY FILTERS |
position and confirm that the return |
|
| |
80 75 70 | 65 | (OPTIONAL) | |
air damper adjusts accordingly. The | 85 | 60 |
|
|
| ||
90 | 55 |
| |
|
|
|
damper actuator may take a few | ||
minutes to open or close. | ||
Damper Control | ||
|
This picture shows a typical photohelic setting. Typical settings are 0.0 in. wg for the lower and 0.10 in. wg for the upper pressure setting. The needle in this photo indicates
a negative building pressure. During correct operation, the indicating needle will remain between or near the setting needles.
Pressure Indicating Pressure Setting
Needle Needles
Pressure Setting Knobs
Photohelic Gauge
Modulating
Potentiometer Control - a modulating spring return actuator is used to control the return air amounts. The return air damper modulates from fully open to fully closed based on a signal from a remote potentiometer.
External Signal - a modulating spring return actuator is used to control the return air amounts. Return air damper modulates from fully open to fully closed based on an external
The return air damper will close with a 10 VDC or
20 mA signal. The return air damper should open with
To test potentiometer operation, turn the potentiometer to the two extremes. Confirm that the return air damper fully opens and fully closes. When the potentiometer is at 0, the return air damper will open. When the potentiometer is at 100, the return air damper will close. The damper actuator may take a few minutes to open or close.
BLOWERS
EXHAUST
(OPTIONAL)
SUPPLY
MAIN VALVES
HEAT
DIRTY FILTERS
(OPTIONAL)
Potentiometer
Control
a 2 VDC or 4mA signal. The damper actuator may take a few minutes to open or close.
®
Model IG / IGX