State Industries SHE50-100PE GAS Pressures, Service Notes Gas Pressure Adjustment, Gas Pressures

Page 18

ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL

GAS PRESSURES (CONT)

CHECKING GAS PRESSURES (CONT)

Typical manifold and supply gas pressures during:

1Standby Mode

2Pre-Purge Mode

3Heating Mode

1BLOWER OFF / GAS VALVE OFF Manifold 0.00” W.C. Supply +9.70” W.C.

Manifold

 

Supply

Gas

 

Gas

2 BLOWER ON / GAS VALVE OFF

Manifold -6.86” W.C. Supply +9.70” W.C.

5Open the supply gas shut off valve - restore power - start a heating cycle.

6The rise in manifold pressure and corresponding drop in supply gas pressure confirms the water heater’s gas valve is opening and gas is flowing to the burner.

7Record the supply and manifold gas pressures with the water heater firing.

8Supply gas pressure should not drop below minimum given in Table 2 below.

9Manifold gas pressure should be within the range shown in Table 2 below.

10Look through the burner view port (page 11) burner flame should be blue.

11Shut off power and gas supply - disconnect manometers - close test port needle valves.

12Restore power and gas supply. Check for gas

3 BLOWER ON / GAS VALVE ON

Manifold +0.05” W.C. Supply +7.04” W.C.

Manifold

Gas

Supply

Gas

Manifold Gas

Supply Gas

Service Notes - Gas Pressure Adjustment

Manifold gas pressure is factory set and should not be adjusted in the field. If manifold gas pressure differs greatly from the pressures in Table 2 consider the calibration of the manometer being used - try a different manometer. Call the technical support phone number on the water heater label for further assistance if pressures are considerably different.

Table 2 - Gas Pressures

FUEL TYPE

MINIMUM SUPPLY

MAXIMUM SUPPLY

MANIFOLD

Natural Gas

3.5” W.C. (0.87 kPa)

14.0” W.C. (3.48 kPa)

0.00” to +0.05” W.C.

(0.00 to +0.012 kPa)

 

 

 

 

 

 

 

Propane Gas

8.0” W.C. (1.99 kPa)

14.0” W.C. (3.48 kPa)

0.00” to +0.05” W.C.

(0.00 to +0.012 kPa)

 

 

 

 

 

 

 

†. Minimum supply gas pressures must be maintained under both load and no load conditions.

Technical Literature Department

17 of 52

Ashland City, TN © 2008

Servicing should only be performed by a Qualified Service Agent

 

Image 18
Contents Service Handbook Ultra High Efficiency Power VENT/POWER Direct Vent Qualifications Qualified Service Agent Service WarningImportant Service Reminder Tools Required Closed Water Systems Thermal ExpansionAIR Requirements Contaminated AIRVenting Maximum Equivalent Length RequirementsMaximum Elbow Requirements Service Notes VentingPipe Size Requirements Number Maximum Pipe Elbows Length Feet MetersCorrectly Wired Outlet Service Notes ElectricalVAC 1Ø Power Supply Electrical RequirementsHOW IT Works Internal ViewService Notes Blower BlowerService Notes Burner Flame Sensor BurnerBurner & Blower Removal On NextService Notes Blower Flange & Blower Adapter Gaskets Burner/Blower RemovalVenturi BlowerGAS Valve Gas Valve RemovalGasket Orifice GAS Pressure Testing Service Notes Checking Gas PressuresService Notes Gas Pressure Adjustment GAS PressuresGas Pressures AIR Pressure Switches Normal State Activated StateBlower Prover Switch Blocked Intake SwitchBlocked Exhaust Switch AIR Pressure Switch Operation Blower Prover FailureAIR Pressure Switch Testing Normal State TestOperational State Test Air Pressure Switch Parameters Pressure TestBlower Prover Blocked Intake Blocked Exhaust Page Flame Sensing Test Measuring Flame Sensing CurrentFlame Sensor Service Notes Hot Surface Igniters Igniter Current TestControl System Features IntroductionService Notes Button Pad Ribbon Cable UIMCommercial & Residential Product Differences Discreet Menu Contact InformationService Note Sequence of Operation Display Desktop ScreenStatus Icons Status Icon DescriptionOperational States Modes State DescriptionOperating SET Point Adjustment Action DisplayControl System Menus ECO Service Notes CCB Replacement CCBJ10 J13 J15 J11 J16 Socket IdentificationJ2 Socket 120 VAC To Blower J3 Socket 120 VAC Power SupplyJ1 Socket Transformer PIN # DescriptionRetry Ext Use Yes Input Type Tstat OpenWiring Diagram Service Notes Polarity & GroundSequence of Operation YESRough Starting Rough Operation Note Resetting the control systemImportant Service Reminder Heater Status MenuUIM is Inoperable Control System UnresponsiveUIM Display Is Blank Displayed Message CHECK/REPAIR CONDITION/INDICATESFault Messages AC ReversedFlame Probe Short Upper Probe ShortFlame Detect Error Energy Cut Out ECOBlocked Inlet Blocked Exhaust Vent Perform ALL These Tests with Power Blower Prover OpenTurned on and a Call for Heat Active Low Igniter Current Ignition Failure Rough Starting Rough Operation NoteCheck for 24 VAC to the Gas Valve solenoid coil Gas Valve Failure Communication FailureTennessee Waltz Parkway Ashland City, TN