State Industries SHE50-100NE Control System Unresponsive, UIM Display Is Blank, UIM is Inoperable

Page 43

ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL

CONTROL SYSTEM UNRESPONSIVE

DISPLAYED MESSAGE

CHECK/REPAIR

CONDITION/INDICATES

 

 

 

UIM Display Is Blank

• Ensure the on/off switch is on and working -

 

replace switch if defective.

On/Off is turned off

• Check communication cable connections at

Water heater is not plugged in

UIM’s J2 Socket (page 27) and the CCB’s J16

Tripped Breaker - Blown Fuses

Socket (page 36). Secure power and install a

120 VAC power supply problems

new comm cable. (standard Cat 5 network

24 VAC power supply problems

cable).

Defective transformer

• Closely inspect communication ports on CCB

Wiring or plug/socket connection problems

and UIM for damage or wear.

UIM communication cable problems

• Ensure 120 VAC power is properly connected in

Important Service Reminder:

the junction box on the back of the water heater.

When performing any troubleshooting steps outlined

• Ensure 120 VAC is supplied to CCB’s J3 Socket

pins 1 & 3. Hot wire to pin 1, neutral wire to pin 3

in this service manual always consider the wiring

(page 36).

and connectors between components. Perform a

• Check 120 VAC to transformer primary winding

close visual inspection of all wiring and connectors

to a given component before replacement.

at CCB’s J1 socket pins 1 & 3 (page 36) with J1

Ensure wires were stripped before being crimped in

plug removed, power on.

• Check J1 plug and J1 socket on the CCB for

a wire connector, ensure wires are crimped tightly in

wear or damage. Ensure plugs and sockets are

their connectors, ensure connection pins in sockets

mating properly and providing good contact.

and plugs are not damaged or worn, ensure plugs

• Check for 24 VAC from transformer secondary

and sockets are mating properly and providing good

contact.

winding at CCB’s J1 socket pins 4 & 5 with J1

 

plug inserted, power on. If 24 VAC is not present

Failure to perform this critical step or failing to

AND the two checks above were performed and

perform this step thoroughly often results in

the results were successful - replace the trans-

needless down time, unnecessary parts

former. Check all wiring for shorts before power-

replacement, and customer dissatisfaction.

ing up the new transformer.

 

• Call the technical support phone number shown

 

on the water heater labeling for further assis-

 

tance if the problem has not been corrected

 

after performing the procedures outlined here.

 

 

UIM is Inoperable

• Ensure Ribbon Cable from the Button overlay is

 

inserted correctly in UIM J3 Socket (page 27).

UIM does not respond to any user input using the

• Call the technical support phone number shown

operational and/or Up and Down buttons.

on the water heater labeling for further assis-

Water heater may be maintaining water temperature

tance if the problem has not been corrected

after performing the procedures outlined here.

at the last saved setting or may not be operating at

 

all.

 

 

 

Technical Literature Department

42 of 52

Ashland City, TN © 2008

Servicing should only be performed by a Qualified Service Agent

 

Image 43
Contents Service Handbook Ultra High Efficiency Power VENT/POWER Direct Vent Service Warning Qualifications Qualified Service AgentImportant Service Reminder Tools Required Thermal Expansion Closed Water SystemsContaminated AIR AIR RequirementsMaximum Equivalent Length Requirements VentingNumber Maximum Pipe Elbows Length Feet Meters Service Notes VentingPipe Size Requirements Maximum Elbow RequirementsElectrical Requirements Service Notes ElectricalVAC 1Ø Power Supply Correctly Wired OutletInternal View HOW IT WorksBlower Service Notes BlowerBurner Service Notes Burner Flame SensorOn Next Burner & Blower RemovalBurner/Blower Removal Service Notes Blower Flange & Blower Adapter GasketsBlower VenturiGas Valve Removal GAS ValveGasket Orifice Service Notes Checking Gas Pressures GAS Pressure TestingGAS Pressures Service Notes Gas Pressure AdjustmentGas Pressures Normal State Activated State AIR Pressure SwitchesBlocked Intake Switch Blower Prover SwitchBlocked Exhaust Switch Blower Prover Failure AIR Pressure Switch OperationNormal State Test AIR Pressure Switch TestingOperational State Test Pressure Test Air Pressure Switch ParametersBlower Prover Blocked Intake Blocked Exhaust Page Measuring Flame Sensing Current Flame Sensing TestFlame Sensor Igniter Current Test Service Notes Hot Surface IgnitersIntroduction Control System FeaturesUIM Service Notes Button Pad Ribbon CableDiscreet Menu Contact Information Commercial & Residential Product DifferencesDesktop Screen Service Note Sequence of Operation DisplayStatus Icon Description Status IconsState Description Operational States ModesAction Display Operating SET Point AdjustmentControl System Menus ECO CCB Service Notes CCB ReplacementSocket Identification J10 J13 J15 J11 J16PIN # Description J3 Socket 120 VAC Power SupplyJ1 Socket Transformer J2 Socket 120 VAC To BlowerExt Use Yes Input Type Tstat Open RetryService Notes Polarity & Ground Wiring DiagramYES Sequence of OperationHeater Status Menu Resetting the control systemImportant Service Reminder Rough Starting Rough Operation NoteDisplayed Message CHECK/REPAIR CONDITION/INDICATES Control System UnresponsiveUIM Display Is Blank UIM is InoperableAC Reversed Fault MessagesUpper Probe Short Flame Probe ShortEnergy Cut Out ECO Flame Detect ErrorBlocked Inlet Blocked Exhaust Vent Blower Prover Open Perform ALL These Tests with PowerTurned on and a Call for Heat Active Low Igniter Current Rough Starting Rough Operation Note Ignition FailureCheck for 24 VAC to the Gas Valve solenoid coil Communication Failure Gas Valve FailureTennessee Waltz Parkway Ashland City, TN