ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL
SEQUENCE OF OPERATION
Call for heat initiated
Air Pressure Switch Test Is Performed Blower Prover Switch is verified open
Blocked Intake and Blocked Exhaust Switches are verified closed
YES
Blower Motor is energized
|
| Blower Prover Switch is verified closed |
|
|
|
|
|
| ||||||
|
|
|
|
| NO | |||||||||
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| YES |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Igniter is energized for warm up period |
|
|
|
|
|
| ||||||
|
|
| (approx 17 seconds) |
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Control System (CCB) Verifies Igniter |
|
|
|
|
|
|
| |||||
|
|
|
|
| NO |
|
| |||||||
|
| Current at 2.0 AC Amps Minimum |
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
| YES |
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Gas Valve Is Energized |
|
|
|
|
|
|
|
| |||
|
|
| Gas Flows To Burner |
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Control System (CCB) Verifies Flame |
|
|
|
|
| |||||||
Sensing Current at 1.0µA DC Micro Amps Minimum |
|
|
|
|
|
|
|
| Control System Declares |
|
|
| Fault Condition - Locks Out |
|
|
| One of the following |
|
|
| Fault Messages Displayed: |
NO |
|
| |
|
| “Blower Prover Failure” | |
|
|
| |
|
|
| “Blocked Inlet” |
|
|
| “Blocked Exhaust Vent” |
|
|
|
|
|
|
|
|
|
|
| Control System Declares |
|
|
| Fault Condition - Locks Out |
|
|
| “Blower Prover Open” |
|
|
| Fault Message Displayed |
|
|
|
|
Control System Declares
Fault Condition - Locks Out
“Low Igniter Current”
Fault Message Displayed
YES
Water Is Heated To
Operating Set Point
Gas Valve Is
30 Sec Approx
Control System Goes Into
Standby State/Mode
NO
Gas Valve Is
30 Sec Approx
Retries Up To
3 Times
Control System Declares Fault Condition - Locks Out
“Ignition Failure”
Fault Message Displayed