Blodgett 900 SERIES manual Gas Connection, GAS Piping, Example, Pipe Nominal Size, Inches Length

Page 15

Installation

Gas Connection

GAS PIPING

A properly sized gas supply system is essential for maximum oven performance. Piping should be sized to provide a supply of gas sufficient to meet the maximum demand of all appliances on the line without loss of pressure at the equipment.

Example:

NOTE: BTU values in the following example are for natural gas.

You purchase a Model 911 deck oven to add to your existing cook line.

1. Add the BTU rating of your current appliances.

Pitco Fryer

120,000

BTU

6 Burner Range

60,000

BTU

Convection Oven

50,000

BTU

Total

230,000

BTU

2.Add the BTU rating of the new oven to the to- tal.

Previous Total

230,000

BTU

911

20,000

BTU

New Total

250,000

BTU

3.Measure the distance from the gas meter to the cook line. This is the pipe length. Let’s say the pipe length is 40’ (12.2 m) and the pipe size is 1” (2.54 cm).

4.Use the appropriate table to determine the to- tal capacity of your current gas piping.

The total capacity for this example is 320,000 BTU. Since the total required gas pressure, 250,000 BTU is less than 320,000 BTU, the current gas piping will not have to be in- creased.

NOTE: The BTU capacities given in the tables are for straight pipe lengths only. Any elbows or other fittings will decrease pipe capaci- ties. Contact your local gas supplier if you have any questions.

Maximum Capacity of Iron Pipe in Cubic Feet

of Natural Gas Per Hour

(Pressure drop of 0.5 Inch W.C.)

Pipe

 

Nominal Size, Inches

 

Length

 

 

 

 

 

(ft)

3/4”

1”

1-1/4”

1-1/2”

2”

 

 

 

 

 

 

 

 

 

 

 

10

360

680

1400

2100

3950

20

250

465

950

1460

2750

 

 

 

 

 

 

30

200

375

770

1180

2200

 

 

 

 

 

 

40

170

320

660

990

1900

 

 

 

 

 

 

50

151

285

580

900

1680

60

138

260

530

810

1520

70

125

240

490

750

1400

 

 

 

 

 

 

80

118

220

460

690

1300

 

 

 

 

 

 

90

110

205

430

650

1220

 

 

 

 

 

 

100

103

195

400

620

1150

 

 

 

 

 

 

From the National Fuel Gas Code Part 10 Table 10-2

Maximum Capacity of Pipe in Thousands of BTU/hr of Undiluted P.P. Gas at 11” W.C.

(Pressure drop of 0.5 Inch W.C.)

Pipe Length

Outside Diameter, Inches

(ft)

 

 

 

3/4”

1”

1-1/2”

 

 

 

 

 

10

608

1146

3525

20

418

788

2423

 

 

 

 

30

336

632

1946

 

 

 

 

40

287

541

1665

50

255

480

1476

60

231

435

1337

 

 

 

 

70

215

404

1241

 

 

 

 

80

198

372

1144

 

 

 

 

90

187

351

1079

 

 

 

 

100

175

330

1014

From the National Fuel Gas Code Part 10 Table 10-15

11

Image 15
Contents Series Avertissement Reputation YOU can Count on Page Table of Contents/Table des Matières Natural Gas Propane Gas US Units SI Units Oven Description and SpecificationsGAS Specifications IntroductionOven Components Oven Location InstallationDelivery and Location Delivery and InspectionOven Assembly Packaging Caster AttachmentLEG Attachment Ultra Rokite Deck Double Section AssemblySteam Injection Gas Flame in oven must be turned off when steam is in useVentilation Canadian installationsGeneral export installations Installing the canopy hood draft diverterVenting Problems Installing the draft hoodDirect Flue Arrangement Utility Connections --- Standards and Codes Pipe Nominal Size, Inches Length Gas ConnectionGAS Piping ExampleKPa Pressure Regulation and TestingInlet Pressure Natural Propane KPa Manifold Pressure Natural PropaneGAS Hose Restraint Initial Startup Adjustments Associated with Initial InstallationOperation Safety InformationSafety Tips General safety tipsOven Control Control DescriptionOperation Fish Product Cook Time MeatsBaked Goods Suggested Times and TemperaturesProduct Cook Time Baked Vegetables CheesePreventative Maintenance MaintenanceCleaning and Preventative Maintenance Cleaning the OvenPossible Causes Suggested Remedy Troubleshooting GuideTroubleshooting Guide Specifications Pour GAZ Description et Spécifications du FourGaz Naturel Gaz Propane Unités US Unités SI Compartiment des brûleurs --- situé au---des Éléments du FourLivraison et Implantation Livraison ET InspectionImplantation DU Four Fixation DES Roulettes Montage du FourEmballage Assemblage DES PiedsDES Plaques EN Rokite Montage DE LA Section DoubleRemarque Injection DE VapeurHotte D’ÉVACUATION Type Voûte Installation aux États-- Unis et au CanadaInstallation du déviateur de tirage AvertissementProblêmes DE LA Ventilation Installation de la hotte de tirageEN Prise Directe Ments brûleursBranchements de Service --- Normes et Codes Exemple Longeur Dimensions nominales De conduit PiedsBranchement de Gaz Conduit DE GAZRéglage ET Test DE Pression Pression à l’entrée Gaz Naturel Gaz PropaneKPa Pression au collecteur Gaz Naturel Gaz Propane Retenue DU Tuyau DE GAZ Réglages À Faire Lors DE L’INSTALLATION Initiale ’Installation InitialeConseils généraux de sécurité UtilisationInformation de Sécurité Conseils DE SécuritéUtilisation Commandes DU FourPoisson Aliment Durée ViandesPains et Patisseries Durées et Températures SuggéréesAliment Durée Légumes cuits au four FromageEntretien Préventif EntretienNettoyage et Entretien Préventif Nettoyage DES FoursCauses Probables Suggestion Guide de Détection des PannesGuide de Détection des Pannes