Blodgett 900 SERIES manual Pressure Regulation and Testing, Inlet Pressure Natural Propane, KPa

Page 16

Installation

Gas Connection

PRESSURE REGULATION AND TESTING

900 Series ovens are rated from 20,000 to 50,000 BTU/Hr. (6.4 to 14.6 kW/Hr.) per section. Each oven has been adjusted at the factory to operate with the type of gas specified on the rating plate.

Inlet Pressure

 

Natural

Propane

 

 

 

 

 

 

 

 

Min

 

Max

Min

 

Max

 

 

 

 

 

 

 

W.C.

7.0

 

10.5

11.0

 

13.0

 

 

 

 

 

 

 

kPa

1.43

 

2.61

2.74

 

3.23

 

 

 

 

 

 

Manifold Pressure

 

 

 

 

 

 

 

Natural

Propane

 

 

 

 

 

W.C.

 

5.0

 

10.0

 

 

 

 

 

kPa

 

1.24

 

2.49

DInlet Pressure --- the pressure of the gas before it reaches the oven.

DManifold Pressure --- the pressure of the gas as it enters the main burner(s).

DMin --- the minimum pressure recommended to operate the oven.

D Max --- the maximum pressure at which the manufacturer warrants the oven’s operation.

Each oven is supplied with a regulator to maintain the proper gas pressure. The regulator is essen- tial to the proper operation of the oven and must be installed. It is preset to provide the oven with 3.5” W.C. (0.87 kPa) for natural gas and 10.5” W.C. (2.50 kPa) for Propane at the manifold.

DO NOT INSTALL AN ADDITIONAL REGULATOR WHERE THE OVEN CONNECTS TO THE GAS SUPPLY.

Prior to connecting the oven, gas lines should be thoroughly purged of all metal filings, shavings, pipe dope, and other debris. After connection, the oven should be checked for correct gas pressure.

Installation must conform with local codes, or in the absence of local codes, with the National Fuel Gas Code, NFPA54/ANSI Z223.1 ---Latest Edition, the Natural Gas Installation Code CAN/CGA- B149.1 or the Propane Installation Code, CAN/ CGA-B149.2as applicable.

The oven and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.45kPa).

The oven must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas piping system at test pressures equal or less than 1/2 psig (3.45kPa).

12

Image 16
Contents Series Avertissement Reputation YOU can Count on Page Table of Contents/Table des Matières Oven Description and Specifications GAS SpecificationsIntroduction Natural Gas Propane Gas US Units SI UnitsOven Components Installation Delivery and LocationDelivery and Inspection Oven LocationPackaging Caster Attachment Oven AssemblyLEG Attachment Double Section Assembly Ultra Rokite DeckGas Flame in oven must be turned off when steam is in use Steam InjectionCanadian installations General export installationsInstalling the canopy hood draft diverter VentilationInstalling the draft hood Venting ProblemsDirect Flue Arrangement Utility Connections --- Standards and Codes Gas Connection GAS PipingExample Pipe Nominal Size, Inches LengthPressure Regulation and Testing Inlet Pressure Natural PropaneKPa Manifold Pressure Natural Propane KPaGAS Hose Restraint Adjustments Associated with Initial Installation Initial StartupSafety Information Safety TipsGeneral safety tips OperationControl Description Oven ControlOperation Product Cook Time Meats FishSuggested Times and Temperatures Product Cook Time Baked VegetablesCheese Baked GoodsMaintenance Cleaning and Preventative MaintenanceCleaning the Oven Preventative MaintenanceTroubleshooting Guide Possible Causes Suggested RemedyTroubleshooting Guide Description et Spécifications du Four Specifications Pour GAZGaz Naturel Gaz Propane Unités US Unités SI Éléments du Four Compartiment des brûleurs --- situé au---desLivraison ET Inspection Livraison et ImplantationImplantation DU Four Montage du Four EmballageAssemblage DES Pieds Fixation DES RoulettesMontage DE LA Section Double DES Plaques EN RokiteInjection DE Vapeur RemarqueInstallation aux États-- Unis et au Canada Installation du déviateur de tirageAvertissement Hotte D’ÉVACUATION Type VoûteInstallation de la hotte de tirage EN Prise DirecteMents brûleurs Problêmes DE LA VentilationBranchements de Service --- Normes et Codes Longeur Dimensions nominales De conduit Pieds Branchement de GazConduit DE GAZ ExemplePression à l’entrée Gaz Naturel Gaz Propane Réglage ET Test DE PressionKPa Pression au collecteur Gaz Naturel Gaz Propane Retenue DU Tuyau DE GAZ ’Installation Initiale Réglages À Faire Lors DE L’INSTALLATION InitialeUtilisation Information de SécuritéConseils DE Sécurité Conseils généraux de sécuritéCommandes DU Four UtilisationAliment Durée Viandes PoissonDurées et Températures Suggérées Aliment Durée Légumes cuits au fourFromage Pains et PatisseriesEntretien Nettoyage et Entretien PréventifNettoyage DES Fours Entretien PréventifGuide de Détection des Pannes Causes Probables SuggestionGuide de Détection des Pannes