Blodgett 900 SERIES manual Ventilation, Canadian installations, General export installations

Page 12

Installation

Ventilation

Blodgett gas deck ovens are direct fired. Heat and flue products from the burners are introduced di- rectly into the baking compartment. As a result, improper venting can have a detrimental effect on the baking characteristics of the oven. A properly designed ventilation system will allow the oven to function properly, while removing unwanted va- pors and products of combustion from the oper- ating area.

This oven may be vented using either:

DA mechanically driven, canopy type, exhaust hood, or

DA direct flue arrangement.

U.S. and Canadian installations

Refer to your local ventilation codes. In the ab-

sence of local codes, refer to the National ventila- tion code titled, “Standard for the Installation of Equipment for the Removal of Smoke and Grease Laden Vapors from Commercial Cooking Equip- ment”, NFPA-96-Latest Edition.

General export installations

Installation must conform with Local and National installation standards. Local installation codes and/or requirements may vary. If you have any questions regarding the proper installation and/or operation of your Blodgett oven, please contact your local distributor. If you do not have a local dis- tributor, please call the Blodgett Oven Company at 0011-802-860-3700.

THE BLODGETT OVEN COMPANY CANNOT AS- SUME RESPONSIBILITY FOR LOSS OR DAMAGE SUFFERED AS A RESULT OF IMPROPER INSTAL- LATION.

WARNING:

Failure to properly vent the oven can be hazardous to the health of the operator and may result in operational problems, unsatisfactory baking and possible dam- age to the equipment.

Damage sustained as a direct result of im- proper ventilation will not be covered by the Manufacturer’s warranty.

CANOPY TYPE EXHAUST HOOD

A mechanically driven, canopy type exhaust hood is the preferred method of ventilation.

The hood should be sized to completely cover the equipment plus an overhang of at least 6” (15 cm) on all sides not adjacent to a wall. The distance from the floor to the lower edge of the hood should not exceed 7’ (2.1m).

The capacity of the hood should be sized appro- priately with provisions for an adequate supply of make up air. Capacity is generally expressed in ft3/min (CFM). 1 CFM of natural gas burned with just enough air for complete combustion pro- duces 11 CFM of combustion products. In virtually all appliances some excess air is used. This vol- ume of excess air is added to the flue products flowing from the appliance.

NOTE: Consult your local exhaust hood contrac- tor for your specific installation.

Installing the canopy hood draft diverter

Ovens ordered for hood venting are supplied with a draft diverter. Install the draft diverter as follows:

1.Place the diverter over the flue connector with the open area facing the front of the oven. See Figure 6.

2.Secure both ends with the sheet metal screws provided.

Draft Diverter

Front of

Oven

Figure 6

8

Image 12
Contents Series Avertissement Reputation YOU can Count on Page Table of Contents/Table des Matières Oven Description and Specifications GAS SpecificationsIntroduction Natural Gas Propane Gas US Units SI UnitsOven Components Installation Delivery and LocationDelivery and Inspection Oven LocationOven Assembly Packaging Caster AttachmentLEG Attachment Double Section Assembly Ultra Rokite DeckGas Flame in oven must be turned off when steam is in use Steam InjectionCanadian installations General export installationsInstalling the canopy hood draft diverter VentilationVenting Problems Installing the draft hoodDirect Flue Arrangement Utility Connections --- Standards and Codes Gas Connection GAS PipingExample Pipe Nominal Size, Inches LengthPressure Regulation and Testing Inlet Pressure Natural PropaneKPa Manifold Pressure Natural Propane KPaGAS Hose Restraint Adjustments Associated with Initial Installation Initial StartupSafety Information Safety TipsGeneral safety tips OperationOven Control Control DescriptionOperation Product Cook Time Meats FishSuggested Times and Temperatures Product Cook Time Baked VegetablesCheese Baked GoodsMaintenance Cleaning and Preventative MaintenanceCleaning the Oven Preventative MaintenanceTroubleshooting Guide Possible Causes Suggested RemedyTroubleshooting Guide Specifications Pour GAZ Description et Spécifications du FourGaz Naturel Gaz Propane Unités US Unités SI Éléments du Four Compartiment des brûleurs --- situé au---desLivraison et Implantation Livraison ET InspectionImplantation DU Four Montage du Four EmballageAssemblage DES Pieds Fixation DES RoulettesMontage DE LA Section Double DES Plaques EN RokiteInjection DE Vapeur RemarqueInstallation aux États-- Unis et au Canada Installation du déviateur de tirageAvertissement Hotte D’ÉVACUATION Type VoûteInstallation de la hotte de tirage EN Prise DirecteMents brûleurs Problêmes DE LA VentilationBranchements de Service --- Normes et Codes Longeur Dimensions nominales De conduit Pieds Branchement de GazConduit DE GAZ ExempleRéglage ET Test DE Pression Pression à l’entrée Gaz Naturel Gaz PropaneKPa Pression au collecteur Gaz Naturel Gaz Propane Retenue DU Tuyau DE GAZ ’Installation Initiale Réglages À Faire Lors DE L’INSTALLATION InitialeUtilisation Information de SécuritéConseils DE Sécurité Conseils généraux de sécuritéCommandes DU Four UtilisationAliment Durée Viandes PoissonDurées et Températures Suggérées Aliment Durée Légumes cuits au fourFromage Pains et PatisseriesEntretien Nettoyage et Entretien PréventifNettoyage DES Fours Entretien PréventifGuide de Détection des Pannes Causes Probables SuggestionGuide de Détection des Pannes