Smart Distribution Panel with ATS

Installation and Wiring

208V

480V

 

 

 

Maximum Utility Input Over-current

225 A UL-listed Breaker (50kAIC)

 

Protection Required

 

 

Utility Input Connection Type

4W + G

3W + G or 4W+G

Size of upstream utility circuit breaker

250 A

200 A

Recommended wire size if 30°C

4/0 AWG

3/0 AWG

Recommended wire size if 40°C

300 kcmil

3/0 AWG

Recommended protective earth size

4 AWG

6 AWG

Generator Input Connection Type

4W + G

3W + G or 4W+G

Output power of generator

80 kW

125 kW

Size of generator output breaker

250 A

200 A

Recommended wire size if 30°C

4/0 AWG

3/0 AWG

Recommended wire size if 40°C

300 kcmil

3/0 AWG

Recommended protective earth size

4 AWG

6 AWG

Supply to Generator Heater and Charger

Hard-wire from transformer in ATS to double duplex NEMA

 

5-20 outlet box on generator

 

Recommended wire sizeVoltage

Installation type Input/Output Cabling Rear Access Required NEC Access Clearances

Two 12 AWG stranded copper

120 VAC

Floorstanding secured to wall (concrete screws included) Top and bottom routing

No

Three feet to an insulated surface

Three feet to grounded parts, including concrete walls, if 208/120 V

3 1/2 feet to grounded parts, including concrete walls, if 480/277 V

Three feet to other live parts, if 208/120 V

Four feet to other live parts, if 480/277 V

Always follow the National Electrical Code (NFPA 75) or the Canadian Electrical Code (CSA C22.1-02) and local codes when installing the InfraStruXure Power Generation System. The AC Power Input wire sizes provided in this document are recommendations only. The ATS is provided with a panel board to supply power to multiple loads. Since loading could increase after the product’s initial installation, the AC Power Input wires were selected for the maximum current that can be delivered by the panel board. If the ATS is purchased to supply a calculated load rated less than the panel board, and the load will never increase, smaller wires can be used if the requirements specified in the NEC, the CEC, and local codes are followed.

††Wire sizes to loads shall be in accordance with the ratings of the circuit breakers selected to power the loads.

78

InfraStruXure Power Generation System

Page 88
Image 88