Smart Distribution Panel with ATS
Installation and Wiring | 208V | 480V |
|
|
|
Maximum Utility Input | 225 A |
|
Protection Required |
|
|
Utility Input Connection Type | 4W + G | 3W + G or 4W+G |
Size of upstream utility circuit breaker | 250 A | 200 A |
Recommended wire size if 30°C† | 4/0 AWG | 3/0 AWG |
Recommended wire size if 40°C† | 300 kcmil | 3/0 AWG |
Recommended protective earth size† | 4 AWG | 6 AWG |
Generator Input Connection Type | 4W + G | 3W + G or 4W+G |
Output power of generator | 80 kW | 125 kW |
Size of generator output breaker | 250 A | 200 A |
Recommended wire size if 30°C† | 4/0 AWG | 3/0 AWG |
Recommended wire size if 40°C† | 300 kcmil | 3/0 AWG |
Recommended protective earth size† | 4 AWG | 6 AWG |
Supply to Generator Heater and Charger | ||
|
|
Recommended wire size† Voltage
Installation type Input/Output Cabling Rear Access Required NEC Access Clearances
Two 12 AWG stranded copper
120 VAC
Floorstanding secured to wall (concrete screws included) Top and bottom routing
No
•Three feet to an insulated surface
•Three feet to grounded parts, including concrete walls, if 208/120 V
•3 1/2 feet to grounded parts, including concrete walls, if 480/277 V
•Three feet to other live parts, if 208/120 V
•Four feet to other live parts, if 480/277 V
†Always follow the National Electrical Code (NFPA 75) or the Canadian Electrical Code (CSA
††Wire sizes to loads shall be in accordance with the ratings of the circuit breakers selected to power the loads.