If Source 2 is a Generator that is Not an APC InfraStruXure Generator

Differences in your system from information presented in this manual

The ATS was designed for operation with an APC InfraStruXure generator, and this manual assumes that Source 2 is an APC InfraStruXure generator. If using a non-APC generator instead of an APC generator, almost all references to the “generator” will still be applicable. However, non-APC generators will generally function differently than APC generators. Therefore, the following sections will not apply to your system and should be disregarded:

“Generator start sequence” on page 7

“Generator cool-down” on page 7

“Fuel monitoring/runtime calculation” on page 9

“Communication converter,” (item 4) on page 13

“Resetting automatic operation on the generator” on page 20

“Generator” on page 37

“Fuel Alarm Limits” on page 44

If your installation includes a non-APC generator, the APC Field Service Engineer performing your start-up will configure your ATS to operate with this generator.