Generator

Maintenance Record: Scroll through a list of items that accumulates after the maintenance record is reset, including:

Last Maintenance Date

Operating Days

Engine Starts

Total kWh

Total Runhours

Next Maintenance: View the month and year of the next scheduled maintenance and the number of days remaining until the next scheduled maintenance. Reset the maintenance record so that the data in the Maintenance Record menu returns to zero.

Generator Settings This screen allows you to access the following settings:

Operating Settings

–Start Delay

The amount of time the generator waits after initiation of the start

 

signal before it begins powering the load. This setting is

 

configurable on the generator control panel (default is 0).

–Stop Delay

The amount of time between when the start signal is removed and

 

when the generator stops. This setting is configurable on the

 

generator control panel (default is 0).

–Crank Settings

The following settings can be changed in the generator service

 

menus by service personnel.

 

Crank: Indicates whether the crank cycle is enabled. If the crank

 

cycle is not enabled, the generator will continue attempting to

 

start until the battery dies.

 

Crank Cycles: The number of crank cycles the generator will go

 

through when attempting to start (default is 3).

 

Crank Time: The amount of time the generator will crank during

 

a crank cycle (default is 15 seconds).

 

Rest Time: The amount of time the generator will rest after it

 

cranks during a crank cycle (default is 15 seconds).

NOTE: APC does not recommend changing the default values of the generator settings described above.

Manufacturer Data

–Fuel System

The type of fuel the generator uses (default is diesel).

–Tank Size

The size of the fuel tank on the generator (in gallons or liters).

–Final Assy Date

Date the generator was assembled at the factory.

–Model Number

Generator model number from Cummins®.

–GenSet S/N

The serial number of the generator.

–Voltage Config

Nominal input voltage (208 V or 480 V).

–Alternator Freq

Nominal frequency setting of the alternator output (50 or 60 Hz).

–Gen kW Rating

The power rating of the generator (80 kW or 125 kW).

Gen Output Adjust

–Voltage

Displays the desired alternator output voltage (configurable on the

 

generator control panel).

–Frequency

Displays the desired alternator output frequency (configurable on

 

the generator control panel).

38

InfraStruXure Power Generation System

Page 48
Image 48
American Power Conversion 250 A manual Operating Settings, Manufacturer Data, Gen Output Adjust