ATS/Voltage

ATS Blocking Transfer Blocking: Defines conditions that will prevent the ATS from transferring from Source 1 to Source 2. The following is displayed on the Transfer Blocking screen:

Block Transfer: Lists configured input contacts that will prevent a transfer from occurring.

Map: Choose from the following input contacts to block a transfer:

C1: Contact 1

C2: Contact 2

C3: Contact 3

C4: Contact 4

Apply Now: After you have made changes on this screen, choose this option and press ENTER to save your changes.

Retransfer Blocking: Defines conditions that will prevent the ATS from transferring from Source 2 to Source 1. The following is displayed on the Retransfer Blocking screen:

Block Retransfer: Lists configured input contacts that will prevent a retransfer from occurring.

Map: Choose from the following input contacts to block a retransfer:

C1: Contact 1

C2: Contact 2

C3: Contact 3

C4: Contact 4

Apply Now: After you have made changes on this screen, choose this option and press ENTER to save your changes.

Gen Start Blocking: Defines input contacts that will prevent the generator from starting because of a line failure:

Block Gen Start: Lists configured input contacts that will prevent the generator from starting.

Map: Choose from the following input contacts to block the generator from starting:

C1: Contact 1

C2: Contact 2

C3: Contact 3

C4: Contact 4

Apply Now: After you have made changes on this screen, choose this option and press ENTER to save your changes.

Other Settings S1 Name: Create a unique name for Source 1 (maximum of 9 characters). The default is Utility.

S2 Name: Create a unique name for Source 2 (maximum of 9 characters). The default is Generator.

Preferred: Displays the preferred source (Source 1).

36