AMX NXD-CV5 Testing your Calibration, Touch Panel Calibration Screens, Calibration Test page

Models: NXD-CV5

1 162
Download 162 pages 52.79 Kb
Page 38
Image 38
FIG. 28 Touch Panel Calibration Screens

Panel Calibration

The request to touch the crosshairs is the first on-screen message

Calibration successful is the second on-screen message that appears after the calibration process is completed

On-screen crosshairs used for calibration of the touch device

FIG. 28 Touch Panel Calibration Screens

If the calibration was improperly set and you cannot return to the Calibration

page (through the panel’s firmware); you can then access this firmware page via G4 WebControl where you can navigate to the Protected Setup page and press the Calibrate button through your VNC window.

This action causes the panel to go to the Calibration page seen above, where you can physically recalibrate the actual touch panel again using the above procedures.

Testing your Calibration

1.Press and hold down the on-screen Calibration button for 6 seconds to enter the Calibration Test page (FIG. 29).

On-screen crosshairs is used to verify a proper calibration of the panel

FIG. 29 Calibration Test page

2.Press anywhere on this page to confirm the on-screen crosshairs match your touch points.

3.If the crosshairs do not appear directly below your LCD touch points, press the Back button and recalibrate the panel using the above steps.

4.Exit this Calibration Test page by pressing the Back button to return to the Protected Setup page.

32

5" Modero Widescreen Touch Panel

Page 38
Image 38
AMX NXD-CV5 manual Testing your Calibration, Touch Panel Calibration Screens, Calibration Test page