Battery Management System

USER’S GUIDE

®

Use FTP or SCP to upgrade one Battery Management System Management Card

For you to be able to use FTP to upgrade a single Battery Management System over the network:

The Battery Management System must be connected to the network.

The FTP server must be enabled at the Battery Management System.

The Battery Management System must have its TCP/IP settings (System IP, Subnet Mask, and Default Gateway addresses) configured.

To use FTP to upgrade the Management Card:

1.Open a command prompt window on a computer that is connected to the network. Go to the directory that contains the firmware upgrade files, and list the files. For the directory C:\apc, the commands would be those shown in bold:

C:\>cd\apc

C:\apc>dir

Files listed for a Battery Management System, for example, might be the following:

apc_hw02_aos_264.bin

apc_hw02_app_260.bin

If your APC device is running version 2.0.1 or later of the

AOS firmware already, you may upgrade directly to version

2.1.0or a later version

2.Open an FTP client session:

C:\apc>ftp

163

Page 170
Image 170
APC Battery Management System manual cd\apc, Apchw02aos264.bin Apchw02app260.bin