Battery Management System

USER’S GUIDE

®

Alarm Relay and LED Operation

Situation/Condition

Alarm Relay

Status LEDs

 

 

 

 

 

 

 

 

 

NOTE: Alarm Relay

Normally Open

Management

Batteries

Charger

Environment

operates as a “Fail-

Contacts (de-

Controller

 

 

 

Safe” device that is

energized)

 

 

 

 

energized during

 

 

 

 

 

non-alarmed periods.

 

 

 

 

 

 

 

 

 

 

 

Normal Operations

Closed

On

On

On

On

 

(energized)

 

 

 

 

 

 

 

 

 

 

Management System

Open

Flash

On

On

On

Fault

(de-energized)

 

 

 

 

 

 

 

 

 

 

High or low

Open

On

On

On

Flash

environment

(de-energized)

 

 

 

 

temperature or

 

 

 

 

 

auxiliary environment

 

 

 

 

 

sensor alarm

 

 

 

 

 

 

 

 

 

 

 

Charger Fault - High

Open

On

On

Flash

On

or low charging

 

 

 

 

 

voltage or high ripple

 

 

 

 

 

current

 

 

 

 

 

 

 

 

 

 

 

Connection fuse or

Open

Flash

On

On

On

wiring fault

 

 

 

 

 

 

 

 

 

 

 

Battery Fault - Low

Open

On

Flash

On

On

capacity, high ohmic

 

 

 

 

 

value, shorted cell or

 

 

 

 

 

thermal runaway

 

 

 

 

 

 

 

 

 

 

 

Missing or Faulty

Open

Flash

On

On

On

Sensor

 

 

 

 

 

 

 

 

 

 

 

System off or loss of

Open

Off

Off

Off

Off

input power

 

 

 

 

 

 

 

 

 

 

 