Battery Management System

USER’S GUIDE

®

Calibration menu

Select to calibrate either a String or a Unit.

String. Select the string you wish to calibrate.

String X

Each string will be listed. Select the

string you wish to configure

 

 

 

Ohmic Correction

Set the overall Ohmic Correction

value.

 

 

 

Unit. Select the unit you wish to calibrate.

Unit X (Web interface)

Each unit will be listed.

 

 

DC Voltage Zero

Set to zero with no string current.

 

 

DC Voltage Span

Set to 100, 200, 500, or 1000 A full

 

scale.

 

 

AC Ripple Zero

Set to zero with no string current.

 

 

Ohmic Correction

Set to match calibrated instrument.

 

 

Current Sensor Range

Set to 100, 200, 500, or 1000 A full

 

scale, based on current sensor

 

specifications.

 

 

DC Current Sensor Zero

Set to zero with no string current.

 

 

AC Current Sensor Zero

Set to zero with no string current.

 

 

Tier Ohmic Value

Enter milliohms of cables and

 

connectors within the string to match

 

calibrated instrument.

 

 