Battery Management System

USER’S GUIDE

®

Reset Discharge Voltages

Reset Lowest Discharge Voltages (control console). The lowest discharge voltage is the lowest voltage measured for each battery in a string during discharge. To clear the stored lowest discharge voltage:

1.Select Device Manager

2.Select Reset Discharge Voltages

3.Select Reset Lowest Discharge Voltages

Reset Lowest Discharge Voltages (Web interface). Select this option from the Detailed Status menu of the Battery Management System menu.

Reset Charge Current Deviation Benchmark

Reset Charge Current Deviation Benchmark (control console). The response benchmark indicates the condition of the battery and the connections to it. It is established when the system is commissioned, when the batteries are replaced, or after a discharge.

1.The response benchmark is automatically cleared during a discharge. To clear the stored response benchmark value and force it to be reset, select Device Manager

2.Select Reset Response Benchmark

3.Select Reset Lowest Response Benchmark

Reset Charge Current Deviation Benchmark (Web interface). Select this option from the Detailed Status menu of the Battery Management System menu.