Battery Management System

USER’S GUIDE

®

Temperature Configuration.

Maximum Pilot

The maximum surface temperature of the pilot battery in

Temperature Limit

the string (the battery to which the pilot temperature sensor

 

is attached). Because the Battery Management System

 

equalizes the charge for all batteries in the string, the

 

temperature of the pilot battery is likely to be typical of

 

other batteries in the string. For example, an overheated

 

pilot battery would probably indicate overcharging

 

throughout the string.

 

 

Maximum Ambient

The maximum and minimum allowable temperature of the

Temperature Limit

air surrounding the batteries. See the specifications for

 

your batteries before changing this value.

Minimum Ambient

Temperature Limit

 

Alarm Configuration.

Ripple Current Limit

Ripple current limit is the allowable AC

 

measurement in the battery string. The default

 

setting is 5 A for every 100 amp-hour of capacity.

 

 

Charge Current Limit

Percentage of change in the response current

 

measurement that is allowed before an alarm is

 

indicated.

 

 

Discharge Voltage Limit

The percentage of the lowest individual battery

 

discharge voltage that is allowed relative to the

 

other batteries in the string.

 

 

Automatic Annuciator Reset

When enabled, the external annunciator devices

 

will reset automatically when the condition of an

 

alarm clears. When disabled, the alarm must be

 

reset manually.

 

 

28

Page 35
Image 35