Battery Management System

USER’S GUIDE

®

Configuration menu

Battery Type Selection. Choose nickel-cadmium or lead-acid batteries. Battery Configuration.

Charger Type (Silcon/

A Silcon unit can have two strings per battery management

Other)

master unit. Other requires a battery management master unit

 

for each new string.

 

 

Number of Strings

The number of strings in the system. Silcon may have two

 

battery strings, all other systems will have one.

 

 

Number of Batteries

The number of batteries in each string in the system. The

per String

maximum number of batteries per string is 244 lead-acid

 

batteries or 375 nickel-cadmium batteries for a non-APC

 

Silcon UPS..

 

 

Number of Cells per

The number of cells per battery for nickel-cadmium batteries

Battery

is 1 or 2. The number of cells per battery for lead-acid

 

batteries is 1, 2, 4, or 6.

 

 

Monitor Wire Length

Choose either >50 feet or <50 feet.

 

 

Cell Max Voltage

The maximum recommended voltage per individual battery

Limit

cell. This number multiplied by the total number cells in a

 

string equals the alarm value for the string. A charger alarm

 

occurs if the string voltage exceeds the alarm value.

 

 

Cell Min Voltage Limit

The minimum recommended voltage per individual battery

 

cell. This number multiplied by the number of total cells in a

 

string equals the alarm value for the string. A charger alarm

 

occurs if the string voltage falls below the alarm value.

 

 

Battery Capacity

Enter battery capacity in amp-hours for reference. The amp-

 

hour capacity of a battery should be clearly marked on the

 

actual battery.

 

 