Battery Management System

USER’S GUIDE

®

Alarms

Fault Alarm Criteria

Fault

LED

Fault Criteria

 

 

 

Charger Voltage Low

Charger

Less than 2.1 volts per cell for lead-acid

 

 

batteries, or as set by user.

 

 

 

Charger Voltage High

Charger

Greater than 2.4 volts per cell for lead-acid

 

 

batteries or as set by user.

 

 

 

Shorted Cell

Batteries

Less than ((#Cells/Batt)-1) x (Vstring)

 

 

(#Cells/Batt) x (#Batt/String)

 

 

 

Blown Fuse/Open

Management

Less than ½ volt on first or last battery in a

Connections or Wiring

Controller

string or two consecutive batteries within a

 

 

string.

 

 

 

Low Capacity

Batteries

Any individual battery with more than 20%

 

 

lower voltage than the highest battery in

 

 

the same string during a discharge.

 

 

 

Thermal Runaway

Batteries

Greater than 20% more response current

 

 

than the benchmark, or greater than 95º F

 

 

battery temperature, or as set by the user.

 

 

 

Dryout/Sulfation/Opens

Batteries

Greater than 20% less response current

 

 

than benchmark, or as set by user.

 

 

 

High or Low Operating

Environment

Less than 50° F or greater than 95° F or as

Temperature

 

set by the user.

 

 

 

High Ripple Current

Charger

Greater than 5 amps RMS per ampere-

 

 

hour or as set by the user.

 

 

 

169

Page 176
Image 176
APC Battery Management System manual Alarms, Fault Alarm Criteria, Fault Criteria