Battery Management System

USER’S GUIDE

Interpreting alarm details

For an alarm category:

The Web interface displays detailed alarm data and any configured threshold values on a single page. For the three types of battery alarms, bar graphs are displayed. To view or change the threshold values, you must use the Configuration menu option of the Battery System menu in the Web interface.

The control console displays detailed alarm data through numbered menus.

Values below the low threshold are indicated by the < character, and values above the high threshold are indicated by the > character.

To view or change the threshold values, select Device Manager and then select String Details in the control console.

See Configuration menu to configure alarm details.

Environment alarms.

 

Category

Details

Diagnostics

 

 

 

 

 

Ambient

The air temperature in the

Problem:

 

Temperature

battery string environment

• Uncorrected high temperature can cause

 

 

is above or below

permanent damage to the batteries.

 

 

configured thresholds.

• Uncorrected low temperature can cause a

 

 

Default:

reduction in battery runtime.

 

 

50.0° F (10° C): low

Response: Check temperature control and

 

 

threshold

ventilation systems in the room, and check

 

 

95.0° F (35° C): high

for overheated batteries (usually caused by

 

 

overcharging).

 

 

threshold.

 

 

 

 

 

 

 

 

Input Contacts

Activation of input

Check the status of the external monitoring

 

 

contacts triggers an

device that sent the input signal.

 

 

alarm.

 

®

 

 

 

 

 

 

23