Battery Management System

USER’S GUIDE

®

SNMP

An Access option (Settings in the control console) enables (by default) or disables SNMP. When SNMP is enabled, the Access Control settings allow you to control how each of the four available SNMP channels is used.

To define up to four NMSs as trap receivers, see Trap Receivers; to use SNMP to manage a UPS or an environmental monitor, see the PowerNet® SNMP Management Information Base (MIB)

Reference Guide (.\doc\en\mibguide.pdf) on the APC Battery Management System Utility CD.

Setting

Definition

 

 

Community

This setting defines the password (maximum of 15 characters) which an

Name

NMS that is defined by the NMS IP setting uses to access the channel.

 

 

NMS IP/

Limits access to the NMS specified by a domain name or to the NMSs

Domain

specified by the format used for the IP address:

Name

• A domain name allows only the NMS at that location to have access.

 

 

• 159.215.12.1 allows only the NMS with that IP address to have access.

 

• 159.215.12.255 allows access for any NMS on the 159.215.12 segment.

 

• 159.215.255.255 allows access for any NMS on the 159.215 segment.

 

• 159.255.255.255 allows access for any NMS on the 159 segment.

 

• 0.0.0.0 or 255.255.255.255 allows access for any NMS.

 

 