Diagnostics

 

 

 

Charge Test

When the Battery

Problem: A percentage deviation

 

Management System applied

outside the acceptable range indicates

 

a test current, the batteries

unexplained changes that indicate the

 

listed in the alarm message

need to verify possible problems with the

 

showed a higher than

battery.

 

acceptable percentage

Response: Identify the listed batteries

 

deviation from the previous

 

immediately so that system backup time

 

“benchmarked” values (which

 

is not reduced. Test and verify status of

 

are reset after any

 

the identified batteries immediately.

 

discharge).

 

 

 

 

 

Pilot

Sampling of the surface

Problem: A high temperature alarm may

Temperature

temperature of one battery in

indicate an overheated (overcharged)

s

the string showed a

battery, usually caused by a faulty

 

temperature above the

charger.

 

configured threshold.

Response: If uncorrected, this condition

 

 

 

Default:

can cause permanent damage to the

 

95° F (35° C) (high

batteries. Replace failed batteries.

 

 

 

threshold).

 

 

 

 

Management Controller alarms.

Category

Details

Diagnostics

 

 

 

Blown

The connections between the

Problem: One or more fuses or wires

Connection

Management Controller and

are open.

Fuse

the batteries are open.

Response: Replace the fuse or wire

 

 

 

 

connection in the location indicated in

 

 

the event log.

 

 

 

Missing or

Not all sensors are present

Problem: The system operation is

Defective

and functional.

not reliable without sensor

Sensors

 

information.

 

 

Response: Connect or replace the

 

 

sensor indicated in the event log.

 

 

 

25

Page 32
Image 32
APC Battery Management System manual Management Controller alarms