OperationImportant Owner’s ConsiderationsEngine Oil

NOTICE  Any attempt to crank or start the engine before it has been properly serviced with the recommended coolant or oil will result in equipment failure.

Refer to the Maintenance section for coolant and oil fill information.

Damage to equipment resulting from failure to follow this instruction will void engine and generator warranty.

Automatic Operation

The generator’s control board constantly monitors utility voltage. Should utility voltage drop below a preset level, the control board will signal the engine to crank and start.

When utility voltage is restored above a preset voltage level, the engine is signaled to shut down.

The actual system operation is not adjustable and is sequenced by sensors and timers on the control board, as follows:

Utility Voltage Dropout Sensor

• This sensor monitors utility source voltage.

This engine is shipped from the factory pre-run and filled with non-synthetic oil (API SL 10W-30W). This allows for system operation in a wide range of temperature and climate conditions. Before starting the engine, check oil level and ensure that engine is serviced as described in the Maintenance section.

Coolant System

If utility source voltage drops below about 70 percent of the nominal supply voltage, the sensor energizes a 3 second timer. The timer is used to ‘sense’ brownouts.

Once the timer has expired, the engine will crank and start.

This engine is shipped from the factory filled with a

Utility Voltage Pickup Sensor

will ensure the fuse is properly installed uponREPRODUCTIONcompletion of

50-50 mix of automotive (ethylene glycol) anti-freeze and

This sensor monitors utility voltage. When utility voltage is

water. This will provide optimum year round protection

restored above 80 percent of the nominal source voltage, a

against freezing, boiling and corrosion.

time delay starts timing and the engine will go to engine cool-

Battery

down.

The installer must supply a valve-regulated, rechargeable

Engine Cool-down imer

12 volt DC starting battery. See Battery in Final Installation

 

Considerations in the installation manual.

When utility power is sensed and the load transfers back to

NOT

the utility source, the engine will go into a cool down period

WARNING Battery posts, terminals and related

as described below:

accessories contain lead and lead compounds - chemicals

• If the generator has run for MORE than 5 minutes,

known to the State of California to cause cancer and

once the utility transfer occurs, the engine will

reproductive harm. Wash hands after handling.

continue to run for about 1 minute before shutting

for

down.

 

15 Amp Fuse

• If the generator has run for LESS than 5 minutes, once

The generator’s 15 Amp fuse is critical to correct system

the utility transfer occurs, the engine will continue to

operation. The 15 Amp fuse was removed at the factory to

run until 5 minutes has elapsed before shutting down.

prevent the unit from starting during shipping. Your installer

 

the installation.

 