NOTICE Any attempt to crank or start the engine before it has been properly serviced with the recommended coolant or oil will result in equipment failure.
•Refer to the Maintenance section for coolant and oil fill information.
•Damage to equipment resulting from failure to follow this instruction will void engine and generator warranty.
The generator’s control board constantly monitors utility voltage. Should utility voltage drop below a preset level, the control board will signal the engine to crank and start.
When utility voltage is restored above a preset voltage level, the engine is signaled to shut down.
The actual system operation is not adjustable and is sequenced by sensors and timers on the control board, as follows:
Utility Voltage Dropout Sensor
• This sensor monitors utility source voltage.
This engine is shipped from the factory
•If utility source voltage drops below about 70 percent of the nominal supply voltage, the sensor energizes a 3 second timer. The timer is used to ‘sense’ brown‑outs.
•Once the timer has expired, the engine will crank and start.
This engine is shipped from the factory filled with a | Utility Voltage Pickup Sensor |
will ensure the fuse is properly installed uponREPRODUCTIONcompletion of | |
This sensor monitors utility voltage. When utility voltage is | |
water. This will provide optimum year round protection | restored above 80 percent of the nominal source voltage, a |
against freezing, boiling and corrosion. | time delay starts timing and the engine will go to engine cool- |
Battery | down. |
The installer must supply a | Engine |
12 volt DC starting battery. See Battery in Final Installation |
|
Considerations in the installation manual. | When utility power is sensed and the load transfers back to |
NOT | the utility source, the engine will go into a cool down period |
WARNING Battery posts, terminals and related | as described below: |
accessories contain lead and lead compounds - chemicals | • If the generator has run for MORE than 5 minutes, |
known to the State of California to cause cancer and | once the utility transfer occurs, the engine will |
reproductive harm. Wash hands after handling. | continue to run for about 1 minute before shutting |
for | down. |
|
15 Amp Fuse | • If the generator has run for LESS than 5 minutes, once | |
The generator’s 15 Amp fuse is critical to correct system | ||
the utility transfer occurs, the engine will continue to | ||
operation. The 15 Amp fuse was removed at the factory to | ||
run until 5 minutes has elapsed before shutting down. | ||
prevent the unit from starting during shipping. Your installer | ||
| ||
the installation. |
|