Delta Electronics VFD-S manual 5-00, 5-01, 5-02, 5-03, 5-04, 5-05, 5-06

Models: VFD-S

1 185
Download 185 pages 61.91 Kb
Page 104
Image 104
5-00

 

 

 

Chapter 5 ParametersVFD-S Series

Group 5: Multi-step Speeds and PLC (Process Logic Control) Parameters

 

 

 

 

5-00

1st Step Speed Frequency

Unit: 0.01

 

5-01

2nd Step Speed Frequency

Unit: 0.01

5-02

3rd Step Speed Frequency

Unit: 0.01

 

5-03

4th Step Speed Frequency

Unit: 0.01

 

5-04

5th Step Speed Frequency

Unit: 0.01

 

5-05

6th Step Speed Frequency

Unit: 0.01

 

5-06

7th Step Speed Frequency

Unit: 0.01

 

 

Settings

d0.0 to d400 Hz

Factory Setting: 0.00

 

 

 

 

 

The Multi-Function Input Terminals (refer to Pr.4-04 to 4-08) are used to select one of the AC

drive Multi-Step speeds. The speeds (frequencies) are determined by Pr.5-00 to 5-06 shown

above.

5-07PLC Mode

 

 

Factory Setting: d0

Settings

d0

Disable PLC operation

 

d1

Execute one program cycle

 

d2

Continuously execute program cycles

 

d3

Execute one program cycle step by step

 

d4

Continuously execute program cycles step by step

 

d5

Disable PLC operation, but can set direction of 1st speed to 7th

 

 

speed

This parameter selects the mode of PLC operation for the AC drive. The PLC program can

be used in lieu of any External Controls, Relays or Switches. The AC drive will change

speeds and directions according to the user’s desired programming.

When this parameter is set to d5 and it is running by external multi-speed, the high priority of

the operation direction is Pr. 5-08.

Example 1 (Pr.5-07 = d1): Execute one cycle of the PLC program. Its relative parameter settings are:

1.Pr.5-00 to 5-06: 1st to 7th step speed (sets the frequency of each step speed).

2.Pr.4-04 to 4-08: Multi-Function Input Terminals (set one multi-function terminal as d17- PLC auto-operation).

3.Pr.3-05 to 3-06: Multi-Function Output Terminals (set a Multi-Function Terminal as d10-PLC operation indication, d11-one cycle in PLC auto mode or d12-PLC operation fulfillment attainment).

4.Pr.5-07: PLC mode.

5.Pr.5-08: Direction of operation for Master Frequency and1st to 7th step speed.

6.Pr.5-09 to 5-16: operation time setting of Master Frequency and1st to 7th step speed.

Revision August 2008, SE09, SW V2.61

5-47

Page 104
Image 104
Delta Electronics VFD-S manual 5-00, 5-01, 5-02, 5-03, 5-04, 5-05, 5-06