Delta Electronics VFD-S manual Over-voltage Stall Prevention, Over-current Stall Prevention Level

Models: VFD-S

1 185
Download 185 pages 61.91 Kb
Page 110
Image 110
Over-voltage Stall Prevention
6-02

 

 

Chapter 5 ParametersVFD-S Series

 

DC bus voltage

 

Over-voltage

Band=20V

detection

level Pr.6-01

 

 

Output

time

 

 

 

Freq.

 

 

 

time

 

Over-voltage Stall Prevention

Over-Current Stall Prevention Level

Unit: 1

Settings

d20 to d150%

Factory Setting: d130

A setting of 100% is equal to the Rated Output Current of the drive.

During acceleration and steady-state operation, the AC drive output current may increase abruptly to exceed the value specified by Pr.6-02 due to rapid acceleration or excessive load on the motor. When this function is enabled, the AC drive will decrease. The AC drive will only resume acceleration when the current drops below the level specified by Pr. 6-02.

Output current

 

Over-current

ON Band=5%

detection

level

OFF

Pr.6-02

 

 

time

Output

 

frequency

 

time

Over-current Stall Prevention Level

Revision August 2008, SE09, SW V2.61

5-53

Page 110
Image 110
Delta Electronics VFD-S manual Over-voltage Stall Prevention, Over-current Stall Prevention Level