Delta Electronics VFD-S manual Display Pr.0-04=d1 TRG, Pr. 3-05 to Pr. 3-06=d15

Models: VFD-S

1 185
Download 185 pages 61.91 Kb
Page 90
Image 90
Display (Pr.0-04=d1)

Display (Pr.0-04=d1)

TRG

Counter Trigger Signal Multi-function Input Terminal

Preliminary Counter Value Attained Output (Pr. 3-04=d3)

(Pr. 3-05 to Pr. 3-06=d15)

Terminal Count Value Attained Output (Pr.3-03=d5)

(Pr.3-05 to Pr.3-06=d14)

Chapter 5 ParametersVFD-S Series

Counter Trigger Signal Multi-function Input TerminalPreliminary Counter Value Attained Output (Pr. 3-04=d3) 2ms (Pr. 3-05 to Pr. 3-06=d15)Terminal Count Value Attained Output (Pr.3-03=d5)

(Pr.3-05 to Pr.3-06=d14) 2ms  2ms 3-06

The width of trigger signal should not be less than 2ms(<250 Hz)

3-05Multi-function Output Terminal 1 (Photocoupler output)

Factory Setting: d1

3-06

Multi-function Output Terminal 2 (relay output)

 

 

 

 

 

 

 

Factory Setting: d8

 

 

 

 

 

 

 

 

 

 

Settings

d0 to d18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting

 

Function

Description

 

 

d0

 

No Function

 

 

 

 

d1

 

AC Drive Operational

the output terminal will be activated when the drive is

 

 

 

 

 

 

running.

 

 

d2

 

Master Frequency Attained

the output will be activated when the AC drive attains

 

 

 

 

 

Maximum Output Frequency.

 

 

 

 

 

 

 

 

d3

 

Zero Speed

the output will be activated when Command Frequency

 

 

 

 

 

 

is lower than the Minimum Output Frequency.

 

 

d4

 

Over Torque Detection

the output will be activated as long as the over-torque is

 

 

 

 

 

 

detected. Pr.6-04 determines the Over-Torque detection

 

 

 

 

 

 

level.

 

 

d5

 

Base-Block (B.B.) Indication

the output will be activated when the output of the AC

 

 

 

 

 

 

drive is shut off by external Baseblock.

 

 

d6

 

Low-Voltage Indication

the output will be activated when low voltage is detected.

 

 

 

 

 

 

 

 

d7

 

Operation Mode Indication

the output will be activated when the operation of the AC

 

 

 

 

 

 

drive is controlled by External Control Terminals.

 

 

d8

 

Fault Indication

the output will be activated when faults occur (oc, ov,

 

 

 

 

 

 

oH, oL, oL1, EF, cF3, HPF, ocA, ocd, ocn, GF).

 

 

d9

 

Desired Frequency Attained

the output will be activated when the desired frequency

 

 

 

 

 

 

(Pr.3-02)is attained.

 

Revision August 2008, SE09, SW V2.61

5-33

Page 90
Image 90
Delta Electronics VFD-S manual 3-06, Display Pr.0-04=d1 TRG, Counter Trigger Signal Multi-function Input Terminal