Delta Electronics VFD-S manual Group 4 Input Function Parameters, 4-00, 4-01, 4-02, 4-03, Example

Models: VFD-S

1 185
Download 185 pages 61.91 Kb
Page 92
Image 92
4-00

 

 

 

 

Chapter 5 ParametersVFD-S Series

Group 4: Input Function Parameters

 

 

 

 

 

 

4-00

Potentiometer Bias Frequency

Unit: 0. 1

 

Settings

d0.0 to d100.0%

Factory Setting: d0.0

 

 

 

 

4-01

Potentiometer Bias Polarity

 

 

 

 

 

 

Factory Setting: d0

 

Settings

d0

Positive Bias

 

 

 

 

d1

Negative Bias

 

 

 

 

 

4-02

Potentiometer Frequency Gain

Unit: 1

 

Settings

d1 to d200%

Factory Setting: d100

 

 

 

 

4-03

Potentiometer Reverse Motion Enable

 

 

 

 

 

 

Factory Setting: d0

 

Settings

d0

Forward motion only

 

 

 

 

d1

Reverse motion enable (must be negative bias)

 

 

 

 

 

 

Pr.4-00 to Pr.4-03 are used when the source of frequency command is the analog signal (0 to +10V DC or 4 to 20 mA DC). Refer to the following examples.

Example 1:

The following is the most common method. Set parameter 2-00 to d1 (0 to +10V signal) or d2 (4 to 20mA current signal).

Example 2:

In this example with the potentiometer set to 0V the Output Frequency is 10 Hz. The mid-point of the potentiometer becomes 40 Hz. Once the Maximum Output Frequency is reached any further increase of the potentiometer will not increase output frequency.

Revision August 2008, SE09, SW V2.61

5-35