The length of motor cable

Appendix B AccessoriesVFD-S Series

The length of motor cable

When motor is driven by an AC motor drive of PWM type, the motor terminals will experience surge voltages easily due to components conversion of AC motor drive and cable capacitance. When the motor cable is very long (especially for the 460V series), surge voltages may reduce insulation quality. To prevent this situation, please follow the rules below:

„Use a motor with enhanced insulation.

„Connect an output reactor (optional) to the output terminals of the AC motor drive

„The length of the cable between AC motor drive and motor should be as short as possible (10 to 20 m or less)

„For models 7.5hp/5.5kW and above:

Insulation level of motor

1000V

1300V

1600V

460VAC input voltage

66 ft (20m)

328 ft (100m)

1312 ft (400m)

230VAC input voltage

1312 ft (400m)

1312 ft (400m)

1312 ft (400m)

„For models 5hp/3.7kW and less:

Insulation level of motor

1000V

1300V

1600V

 

 

 

 

460VAC input voltage

66 ft (20m)

165 ft (50m)

165 ft (50m)

 

 

 

 

230VAC input voltage

328 ft (100m)

328 ft (100m)

328 ft (100m)

 

 

 

 

Manual backgroundManual backgroundManual backgroundManual backgroundNOTE

When a thermal O/L relay protected by motor is used between AC motor drive and motor, it may malfunction (especially for 460V series), even if the length of motor cable is only 165 ft (50m) or less. To prevent it, please use AC reactor and/or lower the carrier frequency (Pr. 02-03 PWM carrier frequency).

Manual backgroundManual backgroundManual backgroundManual backgroundNOTE

Never connect phase lead capacitors or surge absorbers to the output terminals of the AC motor drive.