Delta Electronics VFD-S Description of Parameter Settings, Group 0 User Parameters, 0-00, 0-01

Models: VFD-S

1 185
Download 185 pages 61.91 Kb
Page 74
Image 74
5.3 Description of Parameter Settings
Parameter Reset

 

 

 

 

Chapter 5 ParametersVFD-S Series

 

5.3 Description of Parameter Settings

 

 

 

 

Group 0: User Parameters

This parameter can be set during operation.

 

 

 

 

 

 

 

0-00

Identity Code of the AC Motor Drive

 

 

 

 

 

Settings

Read Only

 

Factory setting: d#

 

 

 

 

0-01

Rated Current Display of the AC motor drive

 

 

Settings

Read Only

 

Factory setting: d ##.#

 

 

 

 

 

 

 

Pr. 0-00 displays the identity code of the AC motor drive. The capacity, rated current, rated voltage and the max. carrier frequency relate to the identity code. Users can use the following table to check how the rated current, rated voltage and max. carrier frequency of the AC motor drive correspond to the identity code.

Pr. 0-01 displays the rated current of the AC motor drive. By reading this parameter the user can check if the AC motor drive is correct.

 

115V/230V Series

 

 

 

 

 

 

kW

0.2

0.4

 

0.75

 

1.5

 

2.2

HP

0.25

0.5

 

1.0

 

2.0

 

3.0

Pr.0-00

d0

 

d2

 

d4

 

d6

d8

Rated Output Current (A)

1.6

2.5

 

4.2

 

7.5

 

11.0

Max. Carrier Frequency

 

 

 

 

10kHz

 

 

 

 

 

460V Series

 

 

 

 

 

 

kW

0.4

 

0.75

 

 

1.5

 

2.2

HP

0.5

 

1.0

 

 

 

2.0

 

3.0

Pr.0-00

d3

 

d5

 

 

d7

 

d9

Rated Output Current (A)

1.5

 

2.5

 

 

 

4.2

 

5.5

Max. Carrier Frequency

 

 

 

 

10kHz

 

 

 

 

0-02

Factory Setting: d0

Settings d9 All parameters are reset to factory settings (50Hz, 220V/380V)

d10 All parameters are reset to factory settings (60Hz, 220V/440V)

This setting allows the user to return all parameters to the factory default settings.

0-03Start-up Display Selection

Factory Setting: d0

Settings d0 Display the frequency command value (LED F) d1 Display the actual output frequency (LED H)

Revision August 2008, SE09, SW V2.61

5-17

Page 74
Image 74
Delta Electronics VFD-S manual Description of Parameter Settings, Group 0 User Parameters, 0-00, 0-01, 0-02