6.2 Reset

Chapter 6 Fault Code InformationVFD-S Series

Fault

Fault Descriptions

 

Corrective Actions

Name

 

 

 

 

 

Software protection failure

Return to the factory.

 

 

Keypad will be locked. Turn the power ON after

 

Password is locked.

power OFF to re-enter the correct password. See

 

 

Pr.0-07 and 0-08.

 

 

1.

Check parameter setting (Pr.A-00) and

 

Analog feedback error or

 

AVI/ACI wiring

 

2.

Check for possible fault between system

 

ACI open circuit

 

 

response time and the feedback signal

 

 

 

 

 

 

detection time (Pr.A-08).

 

Phase Loss

Check input phase wiring for loose contacts.

 

PID feedback error

1.

Check PID feedback wiring.

 

2.

Check if the parameter setting is properly set.

 

 

6.2 Reset

There are three methods to reset the AC motor drive after solving the fault:

1.Press STOP/RESET key on keypad.

2.Set external terminal to “RESET” (set one of Pr.4-04~Pr.4-08 to 06) and then set to be ON.

3.Send “RESET” command by communication.

Manual backgroundManual backgroundManual backgroundManual backgroundNOTE

Make sure that RUN command or signal is OFF before executing RESET to prevent damage or

personal injury due to immediate operation.

6-4

Revision August 2008, SE09, SW V2.61

Page 139
Image 139
Delta Electronics VFD-S manual Reset