0-06

 

 

 

 

 

Chapter 5 ParametersVFD-S Series

0-06

Software Version

 

 

 

 

 

Settings

 

Read Only

 

 

 

 

 

 

 

 

 

 

 

 

 

Display

 

d #.#

 

 

 

 

 

 

 

 

0-07

Password Input

 

Unit: 1

 

 

Settings

d0 to d999

 

Factory Setting: d0

 

 

 

 

 

 

 

 

Pr.0-07 and Pr.0-08 work together to provide data security for the AC drive. When Pr.0-08 is set to a value other than 0, a password must be entered to alter the values of parameters. The password is the number set in Pr.0-08, which ranges from 1 to 999. Pr.0-07 is where the password is entered to allow parameter values to be altered.

Display states:

d0: no password / correct password has been input

d1: parameters are locked

 

0-08

Password Set

 

 

Unit: 1

 

 

Settings

d0 to d999

Factory Setting: d0

 

 

 

 

 

 

 

 

Display

0

No password set or successful input in Pr. 0-07

1Password has been set

To set a password to protect your parameter settings.

If the display shows 0, no password is set or password has been correctly entered in Pr.0-07. All parameters can then be changed, including Pr.0-08.

The first time you can set a password directly. After successful setting of password the display will show 1.

Be sure to record the password for later use.

To cancel the parameter lock, set the parameter to 0 after inputting correct password into Pr. 0-07.

The password consists of min. 1 digits and max. 3 digits.

How to make the password valid again after decoding by Pr.0-07:

Method 1: Re-input original password into Pr.0-08 (Or you can enter a new password if you want to use a changed or new one).

Method 2: After rebooting, password function will be recovered.