Chapter 5 ParametersVFD-S Series

Pr.

Explanation

Settings

Factory

NOTE

Setting

 

d35: Reserved

 

 

 

d36: PID error (Pld)

 

 

 

d37: Reserved

 

 

 

d38: Phase loss (PHL)

 

 

Group 7 Motor Parameters

Pr.

Explanation

Settings

Factory

NOTE

 

 

 

Setting

 

7-00

Motor Rated Current

d30 to d120%

d85

 

7-01

Motor No-Load Current

d0 to d90%

d50

 

7-02

Torque Compensation

d0 to d10

d1

 

7-03

Slip Compensation

d0.0 to d10.0

d0.0

 

Group 8 Special Parameters

 

 

 

 

 

 

 

 

Pr.

Explanation

Settings

Factory

NOTE

Setting

8-00

DC Brake Voltage Level

d0 to d30%

d0

 

8-01

DC Brake Time during Start-Up

d0.0 to d60.0 Sec

d0.0

 

8-02

DC Brake time during Stopping

d0.0 to d60.0 Sec

d0.0

 

8-03

Start-Point for DC Brake

d0.0 to d400 Hz

d0.0

 

 

 

d0: Operation stops after

 

 

 

 

Momentary Power Loss

 

 

 

 

d1: Operation continues after

 

 

 

Momentary Power Loss Operation

momentary power loss, speed

 

 

8-04

search starts with the Master

d0

 

Selection

Frequency reference value

 

 

 

 

 

 

d2: Operation continues after

 

 

 

 

momentary power loss, speed

 

 

 

 

search starts with the minimum

 

 

 

 

frequency

 

 

8-05

Maximum Allowable Power Loss Time

d0.3 to d5.0 Sec

d2.0

 

8-06

B.B. Time for Speed Search

d0.3 to d5.0 Sec

d0.5

 

8-07

Current Limit for Speed Search

d30 to d200%

d150

 

8-08

Skip Frequency 1 Upper Limit

d0.0 to d400 Hz

d0.0

 

8-09

Skip Frequency 1 Lower Limit

d0.0 to d400 Hz

d0.0

 

8-10

Skip Frequency 2 Upper Limit

d0.0 to d400 Hz

d0.0

 

8-11

Skip Frequency 2 Lower Limit

d0.0 to d400 Hz

d0.0

 

8-12

Skip Frequency 3 Upper Limit

d0.0 to d400 Hz

d0.0

 

8-13

Skip Frequency 3 Lower Limit

d0.0 to d400 Hz

d0.0

 

8-14

Auto Restart After Fault

d0 to d10

d0

 

8-15

AVR Function

d0: Enable

d2

 

d1: Disable

 

 

 

d2: Disable when deceleration

 

 

8-16

Software Brake Level

115V/230V series: d350 to d450V

d380

 

 

460V series: d700 to d900V

d760

 

 

 

 

8-17

DC Brake Lower Bound Limit

d0.0 to d400 Hz

d0.0

 