Fault

 

 

 

Chapter 6 Fault Code InformationVFD-S Series

Fault

Fault Descriptions

 

Corrective Actions

 

Name

 

 

 

 

 

 

 

1.

Short-circuit at motor output: Check for

 

 

 

possible poor insulation at the output line.

 

Over-current during

2.

Sudden increase in motor loading: Check for

 

 

possible motor stall.

 

constant speed operation

 

 

3.

AC motor drive output power is too small:

 

 

 

 

 

Replace the AC motor drive with the next

 

 

 

higher power model.

 

 

 

 

 

 

1.

When multi-function input terminals (M1-M5)

 

 

External Fault

 

are set to external fault, the AC motor drive

 

 

stops output U, V and W.

 

 

2.

Give RESET command after fault has been

 

 

 

cleared.

Internal EEPROM can not be

Return to the factory.

programmed.

 

Internal EEPROM can not be

Return to the factory.

programmed.

 

OH error

 

OV error

 

LV error

Return to the factory.

Drive’s internal circuitry

 

abnormal.

 

 

 

 

When (one of) the output terminal(s) is grounded,

 

short circuit current is more than 50% of AC motor

 

drive rated current, the AC motor drive power

 

module may be damaged.

Ground fault

NOTE: The short circuit protection is provided

for AC motor drive protection, not for

 

protection of the user.

1.Check whether the IGBT power module is damaged.

2.Check for possible poor insulation at the output line.

 

1.

When the external input terminal (B.B) is

External Base Block.

 

active, the AC motor drive output will be

 

turned off.

(Refer to Pr. 8-06)

 

2.

Deactivate the external input terminal (B.B) to

 

 

 

operate the AC motor drive again.

 

1.

Check if the motor is suitable for operation by

Auto accel/decel failure

 

AC motor drive.

2.

Check if the regenerative energy is too large.

 

 

3.

Load may have changed suddenly.

 

1.

Check the RS485 connection between the AC

 

 

motor drive and RS485 master for loose wires

 

 

and wiring to correct pins.

Communication Error

2.

Check if the communication protocol, address,

 

transmission speed, etc. are properly set.

 

 

 

3.

Use the correct checksum calculation.

 

4.

Please refer to group 9 in the chapter 5 for

 

 

detail information.