Image 102
d20 Counter Reset:

Chapter 5 ParametersVFD-S Series

d20 Counter Reset:

Parameter value d20 programs Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr. 4-05), M3 (Pr.4-

06), M4 (Pr.4-07) or M5 (Pr.4-08) to reset the counter.

Reset counter

Reset counterd21 Select ACI / Deselect AVI:d22 PID function disable:d23 JOG FWD:d24 JOG REV: Mx "close": reset counter.

d20 reset the counter value.

GND

d21 Select ACI / Deselect AVI:

Parameter value d21 allows the user to select the input type ACI or AVI via an external switch. AVI is

selected when the contact is open and ACI is selected when the contact is closed. Please note: the

use of this feature will override Pr.2-00 programming and the jumper of the front of the drive must be

moved to the correct location either across the AVI or ACI pin head.

d22 PID function disable:

When input ON with this setting, PID function will be disabled.

d23 JOG FWD:

This function could be operated only when the AC motor drive is stop. The operation direction is forward, which can’t be changed. And it can be stopped by the STOP key on the keypad. When the contact is OFF, the AC motor drive will stop by the JOG decel time. Refer to the Pr.1-13 and Pr. 1- 14 for detail.

d24 JOG REV:

This function could be operated only when the AC motor drive is stop. The operation direction is reverse, which can’t be changed. And it can be stopped by the STOP key on the keypad. When the contact is OFF, the AC motor drive will stop by the JOG decel time. Refer to the Pr.1-13 and Pr. 1- 14 for detail.

d25 The source of master frequency is AVI. (The priority is higher than Pr. 2-00 and d26) d26 The source of master frequency is ACI. (The priority is higher than Pr. 2-00)

d27 Press UP/DOWN key to switch forward/reverse (N.O.) motion:

When this function is enabled, press d27 Press UP/DOWN key to switch forward/reverse (N.O.) motion: key for forward motion and d28 Press UP/DOWN key to switch forward/reverse (N.C.) motion: key to REV (N.O.)

motion. The keys Manual background and Manual background will be disabled.

d28 Press UP/DOWN key to switch forward/reverse (N.C.) motion:

When this function is enabled, press Manual background key for forward motion and Manual background key to REV (N.C.)

motion. The keys Manual background and Manual background will be disabled.

Revision August 2008, SE09, SW V2.61