Delta Electronics VFD-S manual Explanation, Settings, Factory

Models: VFD-S

1 185
Download 185 pages 61.91 Kb
Page 65
Image 65

Chapter 5 ParametersVFD-S Series

Pr.

Explanation

Settings

Factory

NOTE

Setting

 

 

d4: Enabled during running. After

 

 

 

 

the over-torque is detected, stop

 

 

 

 

running.

 

 

6-04

Over-Torque Detection Level

d30 to d200%

d150

 

6-05

Over-Torque Detection Time

d0.1 to d10.0 Sec

d0.1

 

6-06

Electronic Thermal Overload Relay

d0 to d2

d2

 

Selection

 

 

 

 

 

6-07

Electronic Thermal

d30 to d600 Sec

d60

 

 

Characteristic

 

 

 

 

 

d0: No fault

 

 

6-08

Present Fault Record

d1: Over current (oc)

 

 

d2: Over voltage (ov)

 

 

 

 

d3: Over heat (oH)

 

 

 

 

d4: Over load (oL)

 

 

6-09

Second Most Recent Fault Record

d5: Over load (oL1)

 

 

d6: External fault (EF)

 

 

 

 

d7: Reserved

d0

 

 

 

d8: Reserved

 

 

 

 

 

 

 

d9: Excess current during

 

 

 

 

acceleration (ocA)

 

 

6-10

Third Most Recent Fault Record

d10: Excess current during

 

 

deceleration (ocd)

 

 

 

 

 

 

 

 

d11: Excess current during steady

 

 

 

 

state (ocn)

 

 

 

 

d12: Ground fault (GF)

 

 

 

 

d13: Reserved

 

 

 

 

d14: Low voltage (Lv)

 

 

 

 

d15: CPU failure 1 (cF1)

 

 

 

 

d16: CPU failure 2 (cF2)

 

 

 

 

d17: Base block (b.b.)

 

 

 

 

d18: Overload (oL2)

 

 

 

 

d19: Auto acceleration/deceleration

 

 

 

 

failure (cFA)

 

 

 

 

d20: Software protection enable

 

 

 

 

(codE)

 

 

 

 

d21: Reserved

 

 

 

 

d22: CPU failure (cF3.1)

 

 

 

 

d23: CPU failure (cF3.2)

 

 

 

 

d24: CPU failure (cF3.3)

 

 

 

 

d25: CPU failure (cF3.4)

 

 

 

 

d26: CPU failure (cF3.5)

 

 

 

 

d27: CPU failure (cF3.6)

 

 

 

 

d28: CPU failure (cF3.7)

 

 

 

 

d29: Hardware protection failure

 

 

 

 

(HPF.1)

 

 

 

 

d30: Hardware protection failure

 

 

 

 

(HPF.2)

 

 

 

 

d31: Hardware protection failure

 

 

 

 

(HPF.3)

 

 

 

 

d32: Communication time-out

 

 

 

 

(CE10)

 

 

 

 

d33: Reserved

 

 

 

 

d34: Software error (SErr)

 

 

5-8

Revision August 2008, SE09, SW V2.61

Page 65
Image 65
Delta Electronics VFD-S manual Explanation, Settings, Factory