Delta Electronics VFD-S manual External Wiring

Models: VFD-S

1 185
Download 185 pages 61.91 Kb
Page 37
Image 37
2.4.2 External Wiring

Chapter 2 Installation and WiringVFD-S Series

2.4.2 External Wiring

Power Supply

FUSE/NFB

Magnetic contactor

Input AC

Line Reactor

Zero-phase

Reactor

EMI Filter

R/L1

S/L2

T/L3

 

 

DC

 

 

+1

 

 

 

 

 

Choke

+2/B1 Manual background

Brake Resistor

B2 Manual background

U/T1 V/T2 W/T3

Zero-phase

Reactor

Output AC

Line Reactor

Motor

Items

Explanations

Power

Please follow the specific power

supply requirements shown in

supply

Appendix A.

 

 

There may be an inrush current

Fuse/NFB

during power up. Please check the

chart of Appendix B and select the

(Optional)

correct fuse with rated current. Use of

 

 

an NFB is optional.

Magnetic

Please do not use a Magnetic

contactor as the I/O switch of the AC

contactor

motor drive, as it will reduce the

(Optional)

operating life cycle of the AC drive.

 

 

 

 

Used to improve the input power

 

factor, to reduce harmonics and

 

provide protection from AC line

 

disturbances (surges, switching

Input AC

spikes, short interruptions, etc.). AC

Line Reactor

line reactor should be installed when

(Optional)

the power supply capacity is 500kVA

 

or more and or advanced capacity is

 

activated. And the mains wiring

 

distance should be 10m. Refer to

 

Appendix B for details.

 

Zero phase reactors are used to

Zero-phase

reduce radio noise especially when

audio equipment is installed near the

Reactor

inverter. Effective for noise reduction

(Ferrite Core

Common

on both the input and output sides.

Attenuation quality is good for a wide

Choke)

range from AM band to 10MHz.

(Optional)

Appendix B specifies the zero phase

 

 

reactor. (RF220X00A)

EMI filter

To reduce electromagnetic

interference, please refer to Appendix

(Optional)

B for more details.

 

 

 

Brake

Used to reduce the deceleration time

of the motor. Please refer to the chart

resistor

in Appendix B for specific brake

(Optional)

resistors.

 

 

 

Output AC

Motor surge voltage amplitude

depends on motor cable length. For

Line Reactor

applications with long motor cable

(Optional)

(>20m), it is necessary to install a

 

reactor at the inverter output side.

 

 

2-22

Revision August 2008, SE09, SW V2.61

Page 37
Image 37
Delta Electronics VFD-S manual External Wiring