Delta Electronics VFD-S manual „ DC capacity of main circuit

Models: VFD-S

1 185
Download 185 pages 61.91 Kb
Page 153
Image 153
„ DC capacity of main circuit

Chapter 8 Maintenance and InspectionsVFD-S Series

 

 

 

„ DC capacity of main circuit

 

 

 

 

 

 

 

Maintenance

 

Check Items

Methods and Criterion

 

Period

 

 

Daily

Half

One

 

 

 

 

 

 

Year

Year

 

 

 

 

 

 

 

If there is any leakage of liquid,

 

 

 

 

 

change of color, cracks or

Visual inspection

{

 

 

 

deformation

 

 

 

 

 

Measure static capacity when

Static capacity initial value X 0.85

 

{

 

 

required

 

 

 

 

 

 

 

 

 

 

 

 

 

„ Resistor of main circuit

 

 

 

 

 

 

 

Maintenance

 

Check Items

Methods and Criterion

 

Period

 

 

Daily

Half

One

 

 

 

 

 

 

Year

Year

 

 

 

 

 

 

 

If there is any peculiar smell or

 

 

 

 

 

insulator cracks due to

Visual inspection, smell

 

{

 

 

overheating

 

 

 

 

 

 

Visual inspection or measure with

 

 

 

 

If there is any disconnection

multimeter after removing wiring

 

{

 

 

between +1/+2 ~ -

 

 

 

 

 

 

 

 

 

Resistor value should be within ± 10%

 

 

 

„Transformer and reactor of main circuit

 

 

Maintenance

Check Items

Methods and Criterion

 

Period

 

Daily

Half

One

 

 

 

 

Year

Year

 

 

 

 

 

If there is any abnormal vibration

Visual, aural inspection and smell

 

{

 

or peculiar smell

 

 

 

 

 

 

 

 

 

 

 

„Magnetic contactor and relay of main circuit

 

 

Maintenance

Check Items

Methods and Criterion

 

Period

 

Daily

Half

One

 

 

 

 

Year

Year

 

 

 

 

 

If there are any loose screws

Visual and aural inspection. Tighten

{

 

 

screw if necessary.

 

 

 

 

 

 

Check to see if contacts work

Visual inspection

{

 

 

correctly

 

 

 

 

 

 

8-4

Revision August 2008, SE09, SW V2.61

Page 153
Image 153
Delta Electronics VFD-S manual „ DC capacity of main circuit